Tools Needed For Installation; Electrical Requirements - Maytag 36” Electric Modular Downdraft Cooktop Installation Instructions

36” electric modular downdraft cooktop

Advertisement

Before you start...
Proper installation is your responsibility.
A qualified technician
should install this
downdraft
cooktop.
Make sure you
have everything necessary for correct
installation. It 1s the responsibility of the
installer to comply with the installation
clearances
specified on the serial/rating
plate. The serial/rating
plate is located
on the rear wall of the burner box.
Check location where downdraft
cooktop
will be installed. The location should be
away from strong draft areas, such as
windows or doors or strong heating vents
and fans. Before making countertop
cutout,
check that ductwork and cooktop location
will clear cabinet walls, backsplash and rear
wall studs inside cabinet.
Important:
Observe
all
governlng
codes and
ordinances.
Fire Hazard
Do Not obstruct the flow of
combustion
and ventilation
air.
Personal Injury Hazard
Avoid installing cabinet storage
above the cooking surface. tf
cabinets are already installed, avoid
the use of cabinet while cooktop is in
US.
Reaching over a heated cooking
surface could result in a serious burn
or other personal injury.
Electrical Shock Hazard
lt is the customer's responsibility:
l
To contact a qualified electrical
installer.
l
To assure that electrical
installation
is adequate
and in conformance
with National Electrical Code,
ANSIJNFPA 70 - latest edition*, and
all local codes and ordinances.
l
Take special care when drilling
holes into wall for venting. Electrical
wires may be concealed
behind
wall covering.
l
Do Not use this appliance
with any
solid state fan speed control device.
Failure to do so could result in fire,
electrical shock or other personal
injury.
FOR PRODUCT
DIMENSIONS
see Panel C.
See NOTE" for
mlnlmum clearances.
I
2" mln. lo
backsplash of
rear peal
wall
/
18" mln. clearance
urmer cabIn
lo
removed and the
drawer fronts installed
I
Countertop opening
dimensions that are
shown must be used.
Given dimensions
provide 0" clearance.
Mobile home installation
The installation of this cooktop must
conform to the Manufactured
Home
Construction
and Safety Standards, Title
24 CFR, Part 3280 (formerly the Federal
Standard for Mobile Home Construction
and Safety, Tile 24, HUD Part 280) or
when such standard is not applicable.
the Standard for Manufactured
Home
Installation 1982 (Manufactured
Home
Sites, Communtties and Setups), ANSI
A225 l-1987 -
or latest edition, or with
local codes.
Copies of the standards listed above
may be obtained
from:
l
National Fire Protection Association
Batterymarch
Park
Quincy, Massachusetts 02269
"NOTE: 24' min. when bottom 01~
wyWydrtetal
cablnei k
Iii
%b"'
less than 'M
me retar
nl mlllboard
covered wllh not less than No. 28
MSG sheet steel. 0.015' dalnless
deal, 0.024' aluminum of 0.020
copper.
ALL OPENINGS IN THE WALL OR
FLOOR WHERE DOWNDRAFT
COOK-TOP IS TO BE INSTALLED
MUST BE SEALED.
30' mln. cleamnce
between the
top of the cooking piatiorm and
the bottom of an unpmtecied
wood or metal cabinet.
Panels A and B.
B
w DOWNDRAFT COOK-TOP MUST BE
Tools needed for
Electrical
installation:
requirements
IMPORTANT: Save Installation Instructions
for electrical
ins0ector's use.
CONNECTED WITH COPPER WIRE ONLY.
DO NOT USE ALUMINUM WIRE.
C
n
Wire sizes and connections
must
conform to the requirements of the
National Electrical Code, ANSI/NFPA
70 - latest edition*, and all local codes
and ordinances.
Wire sizes and
connections
must conform with the
rating of the appliance.
Copies of the standards listed may be
obtained
from:
l
National Fire Protection Association
Batterymarch
Park
Quincy, Massachusetts 02269
-
//
metal snips
Electrical Shock Hazard
l
Electrical ground is required on this
appliance.
. If cold water pipe is interrupted by
plastic, non-metallic
gaskets or
other insulating materials, Do Not
use for grounding.
. Do Not ground to a gas pipe.
l
Do Not have a fuse in the neutral or
grounding circuit. A fuse in the
neutral or grounding circuit could
result in electrfcal shock.
l
Check with a quatttied electrician
if
you are in doubt as to whether the
appliance
is properly grounded.
Failure to follow these instructions
could result in serious injury or death.
Pipe
wrench
ducttape
or knife
D
n
The flexible armored cable
extending from the appliance
should
be connected
directly to the junction
box. The appliance
should be
connected
to the fused disconnect
(or
circuit breaker) box through flexible
armored or non-metallic
sheathed
copper cable.
L
lf local codes permit and a separate
grounding wire is used, it is
recommended
that a qualifred
electrician
determine that the
grounding path is adequate.
A
n
A three-wire or four-wire, single-
phase, 120/240-volt, &Hz, AC-only
electrical supply (or three-wire or four-
wire, 120/208-volt if specified on the
serial/rating plate) is required on a
separate 40-ampere circuit, fused on
both sides of the line. A time-delay
fuse
or circuit breaker is recommended.
The
fuse size must not exceed the circuit
rating of the appliance
as specified on
the serial/rating plate. The serial/rating
plate is located on the rear wall of the
burner box.
Parts suppIled for
itnstallatgon:
E
n
Locate the junction box to allow
as much slack in the line as possible
between the junction box and
appliance
so that the downdraft
cooktop can be moved if servicing is
ever necessary.
Hold-down
screws are attached.
F
n
A U.L.-listed l/2" conduit
connector
must be provided at the
junction box.
G
w A wiring diagram is located
below the control mounting plate.
Panel A