PENSOTTI PCH 34B-H Instruction Manual page 48

Condensing direct vent gas boiler 116,000 btu input
Table of Contents

Advertisement

36
S
P 07
S
1 8
S
P 08
S
P
.9
ARAMETER NO
Not applicable for premix burner (only for atmospheric burner)
P
.10
ARAMETER NO
Not applicable for premix burner (only for atmospheric burner)
P
.11
ARAMETER NO
Not applicable for premix burner (only for atmospheric burner)
P
.12
ARAMETER NO
Not applicable for premix burner (only for atmospheric burner)
MAINTENANCE INSTRUCTIONS
P
ARAMETER
110V 60Hz
6. Use buttons '+' and '-' to modify the value of the parameter
within the prescribed limits
The default value is 36 = 180 sec = 3 min
7. Press and release button 'S' to confirm. The parameter
number (7) will appear on the display.
110V 60Hz
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER
110V 60Hz
6. Use buttons '+' and '-' to modify the value of the parameter
within the prescribed limits
The default value is 18 = 90 sec = 1.5 min
7. Press and release button 'S' to confirm. The parameter
110V 60Hz
number (8) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
7 – C
ENTRAL HEATING PUMP OVERRUN TIMER
00 = 0 x 5 sec = 0 sec
90 = 90 x 5 sec = 450 sec (7.5 min)
8 – D.H.W
PUMP OVERRUN TIMER
00 = 0 x 5 sec = 0 sec
90 = 90 x 5 sec = 450 sec (7.5 min)
45