PENSOTTI PCH 34B-H Instruction Manual page 47

Condensing direct vent gas boiler 116,000 btu input
Table of Contents

Advertisement

00
110V 60Hz
S
P 04
110V 60Hz
S
01
110V 60Hz
S
P 05
110V 60Hz
S
36
110V 60Hz
S
P 06
110V 60Hz
S
MAINTENANCE INSTRUCTIONS
4 – C
P
ARAMETER
ENTRAL HEATING PUMP
6. Use buttons '+' and '-'to modify the value of the parameter:
00 = standard (3 minute default overrun)
01 = permanent (always running)
7. Press and release button 'S' to confirm. The parameter
number (4) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
5 – W
P
ARAMETER
6. Use buttons '+' and '-' to modify the value of the parameter:
00 = off
01 = on (2 second burner delay upon D.H.W. call)
7. Press and release button 'S' to confirm. The parameter
number (5) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
6 – C
P
ARAMETER
ENTRAL HEATING TIMER
Electronically timed heating differential
6. Use buttons '+' and '-'to modify the value of the parameter
within the prescribed limits
00 = 0 x 5 sec = 0 sec
90 = 90 x 5 sec = 450 sec (7.5 min)
The default value is 36 = 180 sec = 3 min
7. Press and release button 'S' to confirm. The parameter
number (6) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
ATER HAMMER PREVENTION
44