Mitsubishi Electric PKH18FK1 Technical & Service Manual page 35

Series pkh wall mounted/series pch ceiling suspended/series plh ceiling cassettes
Table of Contents

Advertisement

2-2 DRY operation
SWING
TIMER OFF TIMER
CLOCK AUTO AUTO
FAN
CHECK SET TEMP.
START STOP
FILTER
SPEED
AUTO
CHECK MODE
RETURN
TEST RUN
<DRY operation time chart>
Operation starts by
P O W E R b u t t o n
ON.
ON
OFF
Thermostat
ON
Indoor fan
OFF
ON
Auto vane
OFF
ON
Drain pump
OFF
ON
Booster heater
OFF
ON
Compressor
OFF
w 1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
The compressor maintains the previous state when the room temperature minus the set temperature is 0°F or more, or
lower than 2°F.
3 The compressor stops in check mode or during protective functions.
<How to operate>
1 Press POWER ON/OFF button.
2 Press the MODE button to display "DRY"
3 Press the SET TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the SET TEMP.
Room temperature
becomes equal to
set temperature.
DRY MODE
OFF
Minimum 3 minutes w1
OC193-33
button is pressed one time.
Dry 64 to 86°F
Room temperature
Operation stops by
rises above set
P O W E R b u t t o n
temperature.
OFF.
DRY MODE
3 minutes