Weil-McLain GV90+ Installation And Start-Up Manual page 81

Series 2 gas-fired water boilers
Hide thumbs Also See for GV90+:
Table of Contents

Advertisement

GV90+
Series 2
OAS·FIRED WATER BOILER -
Boiler Manual
Troubleshooting
(continued)
Fi
gure
94
Common
causes
and possible
cooections.
part
1
Symptom
Common Causes
Possible Corrections
Rapid cycling - boiler
Thermostat
installed
where drafls
Locate
thennostat
on
inner
wall
away from
turns
on and off frequently
or heat
affect
reading
heat
sources
or
cool
drafts.
Heat
anticipator
in
thennostal
Adjust
thermostat
per
manufacturer's
a~usted
inoorrectly
instructions.
Incorrect
limit
setting
Set
limit
aooording
to
system
needs.
Maximum
setting
is
2oo•F.
Increase
limit
setting
to
decrease
cycling.
Insufficient
water
flow t hrough
Check all
valves
to and from
boiler.
Return
boiler
to
proper
setting.
Confirm
circulator
size.
Frequent release
of water
Expansion
tank
sized too
small
Call
quatKied service technician to
chec·k
through
relie
f
valve
expansion tank
operation
and
size.
Aooded
expansion
tank
Call
quatKied service technician to
chec·k
expansion tank
operation.
Inoperative
limit
control
Call
quatKied service technician to replace
limit
control.
Need to
frequently
add
Leaks
in
boiler or
piping
Have
qualified
service technician
repair
makeup water
leaks
at once
to
avoid
constant use
of
makeup
water.
Makeup
water
can
ceuse
mineral
deposits which,
in
turn,
can
cause
boiler
section
failure.
Do
not use
petroleum-
base
slop-leak
compounds.
Black water condition
Oxygen
oorrosion
due
to
leaks
in
Have
qualified service
technician repair at
boiler
and
piping
once.
Keep pH
of
water
between 7.0
to
8.5.
Large
t
empe
rature
swings
Incorrect
Eoonomy
seHing
Adjust
Economy
seHing
on
boiler
oontrol.
in living
space
Part
number
550-14-2-783/1012
St

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qv90+3Ov90+4Qv90+5Ov90+6