5
Fan replacement in a Brocade VDX 6740T and Brocade VDX 6740T-1G
Fan replacement in a Brocade VDX 6740T and Brocade VDX
6740T-1G
The Brocade VDX 6740T and Brocade VDX 6740T-1G have five fans as displayed in
Network OS identifies the fan locations from left to right as fan #1, fan #2, fan #3, fan #4, and fan
#5 when viewed from the non-port side of the switch.
1
2
3
FIGURE 17
ATTENTION
Maintain all power supplies and fans in operational condition to provide redundancy.
CAUTION
Because the cooling system relies on pressurized air, do not leave any of the power supply or fan
slots empty longer than two minutes while the switch is operating. If a power supply or fan
assembly fails, leave it in the switch until it can be replaced.
CAUTION
Disassembling any part of the power supply or fan assembly voids the warranty and regulatory
certifications. There are no user-serviceable parts inside the power supply or fan assembly.
42
•
show chassis
•
show environment power
The power supply status can also be viewed using the Web Tools application.
Fan #1
Fan #2
Fan #3
Brocade VDX 6740T and Brocade VDX 6740T-1G fan assemblies on the non-port side
4
Fan #4
5
Fan #5
6
Captive screw (same location for each fan)
Brocade VDX 6740 Hardware Reference Manual
Figure
17. The
53_1002829_02