Chassis Ground Connection; Ac Power Supply Wiring Example; Wiring For Single Ac Power Supply (Hip Module Shown) - RuggedCom RuggedBackbone RX1501 Hardware Installation Manual

Rugged layer 3 switch and router
Hide thumbs Also See for RuggedBackbone RX1501:
Table of Contents

Advertisement

3. Installation

3.2.3. Chassis Ground Connection

The RX1501 chassis ground connection, shown in
uses a #10-32 screw. It is recommended to terminate the ground connection in a #10 ring lug.
Torque on the chassis ground connection should not exceed 30 in-lbs (3.4 Nm).
Figure 3.12. Chassis Ground Connection

3.2.4. AC Power Supply Wiring Example

Figure 3.13. Wiring for Single AC Power Supply (HIP module shown)
• For 125/230VAC rated equipment, a appropriately rated AC circuit breaker must be
installed.
• It is recommended to provide a separate circuit breaker for each power supply
module.
• Equipment must be installed according to applicable local wiring codes.
RuggedCom® RuggedBackbone™
Figure 3.12, "Chassis Ground
23
RX1501 Installation Guide Rev 104
Connection",