4. Position the wallplate over the holes, pulling wires
through the wiring opening. See Fig. 7.
5. Insert the mounting screws into the holes and tighten.
WALL
WIRES THROUGH WALL
AND WIRE SLOT
MOUNTING
HOLES
MOUNTING
SCREWS (2)
Fig. 7. Mounting wallplate.
Installing Equipment Interface Module (EIM)
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The EIM can be mounted vertically on the HVAC equipment or
on a wall in the equipment room.
1. Position the EIM.
2. Use a pencil to mark the mounting holes.
3. Remove the wallplate from the wall and, if drywall, drill
two 3/16-in. holes in the wall, as marked. For firmer
material such as plaster, drill two 7/32-in. holes. Gently
tap anchors (provided) into the drilled holes until flush
with the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Insert the mounting screws into the holes and tighten.
See Fig. 8.
Communication LED
The EIM has an LED (see Fig. 8) that communicates the EIM
status as follows.
• LED blinks rapidly: Normal information transfer.
• LED blinks once: Incoming message to EIM.
• LED blinks continuously: Wiring problem. Check wiring to
terminals 1, 2, 3.
• LED always off: Wiring problem. Check wiring to terminals
1, 2, 3.
• LED always on: EIM may need replacement.
WALL ANCHORS (2)
M23541
M23543
®
VISIONPRO
NOTE: It is normal for the LED to blink continuously during
startup, and while checking equipment status (Auto
Discover mode).

WIRING

All wiring must comply with local electrical codes and
ordinances. See Fig. 10–20.
1. Select set of terminal identifications (Table 1) that corre-
sponds with system type.
2. Loosen the screws for the appropriate system type
selected; see Table 1. See Table 2 for terminal designa-
tion descriptions. Insert wires in the terminal block under
the loosened screw. See Fig. 9.
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to prevent
drafts from affecting the thermostat.
6. See Fig. 10–20 for typical wiring hookups.
Table 1. Selecting Terminal Identifications for System Type.
System Type
Standard Heat/Cool Conventional
Standard Multistage
up to 3 Heat/2 Cool
Heat Pump with
Auxiliary Heat
5
IAQ TOTAL HOME COMFORT SYSTEM
WALL ANCHOR
COMMUNICATION LED
DRILL 3/16 IN. HOLES
FOR DRYWALL. DRILL
7/32 IN. HOLES FOR
PLASTER
MOUNTING SCREW
Fig. 8. Mounting EIM.
Wallplate Terminal
Wiring Diagram
Identifications
Conventional
Heat Pump
M23484
Reference
10, 11
12
13
68-0287—1