Installer System Test - Honeywell VisionPRO IAQ Product Data

Total home comfort system
Hide thumbs Also See for VisionPRO IAQ:
Table of Contents

Advertisement

®
VISIONPRO
IAQ TOTAL HOME COMFORT SYSTEM
ISU
Parameter
Installer Setup
Number
Name
700
Temperature
Display Offset
701
Humidity Display
Offset
710
Restore Factory
Defaults

INSTALLER SYSTEM TEST

Use the Installer System Test to test the heating, cooling and
fan (and emergency heat for heat pump systems).
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
Installer System Test
Avoid cycling compressor quickly.
How to Use the Installer System Test
The Installer Test is part of the Installer Setup Menu.
1. Enter the Installer System Test by entering the Installer
Setup.
2. Note that the test appears at the end of the Installer
Setup Numbers.
3. See Fig. 28 to review how the thermostat buttons are
used during the Installer System Test. See Table 6 for
available Installer System Tests.
4. If installed with a Discharge Air Temperature Sensor
(ISU365=1) press the "MORE" button to view the dis-
charge temperature, and press Cancel to return to the
Installer test screen.
68-0287—1
Table 3. Installer Setup Menu. (Continued)
Settings
(Factory Defaults Shown in Bold)
-3
-3°F
-1.5°C
-2
-2°F
-1°C
-1
-1°F
-.5°C
0
0°F
0. °C — (no difference in displayed
temperature and actual room temperature)
1
1°F
.5°C
2
2°F
1°C
3
3°F
1.5°C
-5
-5%
-4
-4%
-3
-3%
-2
-2%
-1
-1%
0
0%
1
1%
2
2%
3
3%
4
4%
5
5%
0
No
1
Yes
Restoring factory defaults will re-set installer setup and
programming.
SYSTEM TEST
NUMBER
DONE
DONE KEY
EXITS INSTALLER
SYSTEM TEST
Fig. 28. Review thermostat buttons used during Installer
18
Notes
UP ARROW
SYSTEM STATUS
TURNS THE
NUMBER
SYSTEM ON
UP ARROW KEY
DOWN ARROW
ADVANCES TO
TURNS THE
NEXT SYSTEM
SYSTEM OFF
TEST NUMBER
System Test.