C7089U1006 Outdoor Temperature Sensor
Operation
When installed with Thermostat Installer Setup Number 0342
set to 1, the outside temperature can be displayed on the
thermostat. See Fig. 34.
MON
TUE
WED
FAN
Inside
AUTO
SYSTEM
HEAT
SCHED
HOLD
Fig. 34. Outside temperature reading on
VisionPRO
The C7089U1006 Outdoor Sensor converts outdoor ambient
temperature to a resistance that the thermostat can interpret.
The C7089U1006 has a negative temperature coefficient
(NTC), which means that resistance decreases as the
temperature increases. See Table 12.
Checkout
Allow C7089U1006 Outdoor Sensor to absorb outdoor air for a
minimum of twenty minutes before taking a reading.
With an accurate thermometer (±1°F [0.5°C]) measure the
temperature at the sensor location, allowing time for the
thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of the
C7089U1006 60-in. leadwires. Use an ohmmeter to measure
the resistance across the sensor. Then verify the sensor
accuracy with the temperature/resistance in Table 12.
Calibration
The C7089U1006 Outdoor Sensor is calibrated at the factory
and cannot be recalibrated in the field.
THU
FRI
SA
SUN
CLOCK SCREEN
LEAVE
RETURN
SLEEP
CANCEL
M23679
THU
FRI
SAT A A T
SUN
Set To
Following
Schedule
Outside
AM
CLOCK SCREEN
MORE
M22453
®
IAQ Thermostat.
VISIONPRO
Table 12. Sensor Resistance at
Outdoor
Temperature
°F
°C
Resistance
-20
-28.9
-18
-27.8
-16
-26.7
-14
-25.6
-12
-24.4
-10
-23.3
-8
-22.2
-6
-21.1
-4
-20.0
-2
-18.9
0
-17.8
2
-16.7
4
-15.6
6
-14.4
8
-13.3
10
-12.2
12
-11.1
14
-10.0
16
-8.9
18
-7.8
20
-6.7
22
-5.6
24
-4.4
26
-3.3
28
-2.2
30
-1.1
32
0.0
34
1.1
36
2.2
38
3.3
40
4.4
42
5.6
44
6.7
46
7.8
48
8.9
50
10.0
C7189U1005 Remote Indoor Temperature
Sensor
Operation
When installed with Thermostat Installer Setup Number 0340
set to 1, the remote inside temperature is displayed on the
thermostat home screen as Inside Temperature. The
thermostat internal temperature sensor is not used. When
33
®
IAQ TOTAL HOME COMFORT SYSTEM
Outdoor Temperature.
Outdoor
Temperature
Ohms of
°F
°C
106926
52
11.1
100923
54
12.2
95310
56
13.3
90058
58
14.4
85124
60
15.6
80485
62
16.7
76137
64
17.8
72060
66
18.9
68237
68
20.0
64631
70
21.1
61246
72
22.2
58066
74
23.3
55077
76
24.4
53358
78
25.6
49598
80
26.7
47092
82
27.8
44732
84
28.9
42506
86
30.0
40394
88
31.1
38400
90
32.2
36519
92
33.3
34743
94
34.4
33063
96
35.6
31475
98
36.7
29975
100
37.8
28558
102
38.9
27219
104
40.0
25949
106
41.1
24749
108
42.2
23613
110
43.3
22537
112
44.4
21516
114
45.6
20546
116
46.7
19626
118
47.8
18754
120
48.9
17926
Ohms of
Resistance
17136
16387
15675
14999
14356
13743
13161
12607
12081
11578
11100
10644
10210
9795
9398
9020
8659
8315
7986
7672
7372
7086
6813
6551
6301
6062
5834
5614
5404
5203
5010
4826
4649
4479
4317
68-0287—1