Lennox Elite XP16−024−230 Installation Instructions Manual page 39

Elite xp16 series
Hide thumbs Also See for Elite XP16−024−230:
Table of Contents

Advertisement

TEST
Placing the jumper on the field test pins (P1) allows the technician to:
S
Clear short cycle lockout
S
Clear five−strike fault lockout
S
Cycle the unit in and out of defrost mode
S
Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control's TEST pins for 2 to
5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal
operation.
The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one
second and then reapplied.
Place a jumper on TEST pins for
longer than one second but less
than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable. No other functions will be
executed and unit will continue in the
mode it was operating.
If in COOLING Mode
No further test mode operation will be
executed until the jumper is removed
from the TEST pins and reapplied.
NOTE
Placing a jumper on the TEST pins will not bring the unit
out of inactive mode. The only way manually activate the heat
pump from an inactive mode is to cycle the 24VAC power to the
Control.
Y1 Active
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and
enter HEAT MODE uncalibrated
with defrost timer set for 45 minute
test.
If jumper on TEST pins remains in
place for more than five seconds.
The unit will return to HEAT MODE
un−calibrated with defrost timer set
for 34 minutes.
Figure 27. Test Pin (P1) Functions
Page 39
INACTIVE
If in HEATING Mode
If no ambient or coil sensor fault
exist, unit will go into DEFROST
MODE.
If ambient or coil faults exist (open or
shorted), unit will remain in HEAT
MODE.
If jumper on TEST pins is removed
before a maximum of five seconds.
The unit will remain in DEFROST
MODE until termination on time or
temperature.
XP16 SERIES

Advertisement

Table of Contents
loading

Table of Contents