Gfci Wiring - La-Z-Boy Spas Dream Owner's Manual

La-z-boy premier spas owner’s manual
Table of Contents

Advertisement

WARNING: Disconnect the electrical power before servicing.
Parts with extra low voltage (not exceeding 12V) must be inaccessible to a person in
the spa / hot tub. Earthed appliances must be permanently connected to fixed wiring.
Parts incorporating electrical components must be located or fixed so that they
cannot fall into the spa / hot tub.
Means for disconnection must be used with fixed wiring configurations in accordance
with local wiring rules
IMPORTANT: To allow the GFCI to function properly, connect the white Neutral wire
from the
spa
/ hot tub to the Neutral terminal on the GFCI breaker, not the Neutral bus
in the GFCI breaker box. An improperly connected Neutral causes the GFCI breaker
to trip.
For HELP, call La-Z-Boy
WARNING
Before obtaining access to terminals, all supply circuits
must be disconnected.
.
Figure 3 - GFCI Wiring
Spas at 1.800.465.2933.
®
17

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for La-Z-Boy Spas Dream

This manual is also suitable for:

Soul mateFantasyImagine

Table of Contents