Important: Qualified and licensed electricians must perform all electrical hookups.
The following specifications must be followed in order to ensure proper performance
and safety.
WARNING:Starting an incorrectly wired
CAUTION:
All spa / hot tubs must be wired with a 50 Ampere (A) breaker (or according to IEE wire
regulations for export models). Failure to do so will cause equipment damage and will
not be covered under your guarantee.
All spa / hot tubs must be protected with an over current protective device with built-in
GFCI in the service panel.
Volts
Freq.
(V)
(Hz)
240
60
CAUTION: Test the GFCI before each use of the spa / hot tub.
For HELP, call La-Z-Boy
Electrical Specifications
severe damage to the mechanical equipment or even
bodily harm. Have your licensed
wiring with the schematics on pages 17 - 18 prior to
starting the
spa
Failure to abide by specifications listed may result in
damage to the equipment and will void the warranty.
Rating
Phase
(A)
1
40
Table 2 – Wire Size Chart
* Use only solid copper wire.
Spas at 1.800.465.2933.
®
spa / hot tub
/ hot tub or call your local dealer.
GFCI
Wire size from GFCI
(A)
to Main Panel*
6-3 plus ground (up to 130')
50
4-3 plus ground (up to 230')
2-3 plus ground (up to 360')
16
could cause
electrician verify GFCI
# of
Terminals
on plug
4