Comfort Net ™ System Advanced Features - Goodman CONDENSING UNIT HEAT PUMP Installation & Service Reference

Condensing unit heat pump
Table of Contents

Advertisement

40VA Transformer (included in
CTK0*AA kit)
24 VAC
208/230 VAC
System Wiring using Two-Wires between Furnace and AC/HP
and Four-Wires between Furnace and Thermostat
C
N
™ S
OMFORT
ET
YSTEM
The ComfortNet system permits access to additional system
information, advanced setup features, and advanced diag-
nostic/troubleshooting features. These advanced features
are organized into a menu structure. The menus are ac-
cessed and navigated as described below.
A
N
CCESSING AND
AVIGATING THE
M
ENUS
The advanced system features are accessed using the
ComfortNet™ thermostat. These advanced features are ac-
cessed as follows:
On the CT thermostat Home Screen Display, touch
the Menu key to display additional key choices.
Touch and hold the Installer Config key for
approximately 3 seconds to enter the Thermostat
Options Configuration menu.
Touch and hold the Installer Config key again for
approximately 3 seconds to enter the Advanced
Installer Configuration menu.
Installer
Clean Display
Config
Upon entering the advanced menus, the Advanced Fault Menu
is displayed. The display will change to the Fault Screen and
indicate any faults that may be present in the indoor or outdoor
equipment. If a fault is present, the Fault Screen will show the
equipment and an error code with a description of the fault.
_
Touch
or
keys to view the fault status of any remaining
+
equipment. The text "NO FAULTS" will be scrolled if no errors
are present.
CTK0*AA
1
2
R C
Thermostat
CT Compatible Air
Handler/Furnace/Modular
1
2
R C
Blower Integrated
Control Module
CT Compatible
1
2
R C
AC/HP Integrated
Control Module
A
F
DVANCED
EATURES
A
F
DVANCED
EATURES
Set Time
Run
Set
Sch ed u le
Schedule
Call for Service
Advanced
Menu
Schedule
Touch the
or
_
to step through the list of installed equip-
ment, including the thermostat. Touch the Installer Config
key to enter the submenus for the equipment displayed. The
text "WORKING" will be displayed in the scrolling display
area while the data is being retrieved. The first sub-menu is
then displayed. See tables below for listing of furnace sub-
menus.
Touch the
or
to step through the list of submenus and
_
view settings. If a setting can be adjusted,
will appear. Use the
desired value. Touch the
"WORKING" will appear as the settings are being updated.
"DONE" will appear to indicate the change was accepted. If
the change is not accepted, the display will show "FAIL" then
revert to the Fault Screen.
Some parameters being displayed switch between the item
name and the item value. Touch the Hold key to momen-
tarily stop the display from switching.
To exit an equipment submenu and revert back to the equip-
ment menus, touch the Menu key. Touch Menu again to re-
vert back to the Thermostat Options Menu. Touch the Run
Schedule key to step out of all menus and back to the CT
thermostat Home Screen Display.
If this heat pump is installed with a CT compatible air handler/
modular blower, the system is recognized as a heat pump
system. The electric heat disabled temperature and heat pump
disabled temperature must be set via the thermostat advanced
menu. Navigate to the THERMOSTAT menu. Press the IN-
STALLER CONFIG key. Navigate to the SETUP menu and
press the INSTALLER CONFIG button. Navigate to AUX HT
LOCKOUT. Adjust the electric heat disabled temperature to
the desired setting using the back/forward arrows. Navigate to
HP BAL PNT. Adjust the heat pump disabled temperature to
the desired setting using the back/forward arrows.
D
IAGNOSTICS
Accessing the air conditioner/heat pump's diagnostics menu
provides ready access to the last six faults detected by the air
conditioner/heat pump. Faults are stored most recent to least
recent. Any consecutively repeated fault is stored a maximum
of three times. Example: The power supply to the air condi-
tioner/heat pump is continuously below 187 VAC. The control
will only store this fault the first three consecutive times the
fault occurs. Navigate to the diagnostics menu as described
above in Accessing and Navigating the Advanced Features
Menus.
NOTE: It is highly recommended that the fault history be cleared
when performing maintenance or servicing the heat pump.
11
Call for Service
Run
_
_
or
keys to adjust the setting to the
+
or
_
to step to the next item.
Advanced
Menu
Run
Schedule
and
keys
+

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents