MUST be in the "OFF" position. CAUTION: more than one disconnect may exist. Failure to observe this warning may The CPLE090/120 product operates in the same manner as most result in an electrical shock that can cause serious personal injury residential heat pumps.
Site Selection Prohibited Locations. Do not locate this unit in the following locations: This unit is designed for outdoor installations only. Inside a building Air Supply. The CPLE products are air-cooled heat pumps. To Directly under a vent termination from a gas appliance ensure the optimum unit performance, the installation site should Within 3 feet of a clothes dryer vent provide unobstructed airflow.
50' - 74' 75' - 99' Unit Corner Weight Outside Diameter Line Size (in.) The following table and sketch are to be used for determining CPLE090 1-1/8 1-3/8 1-3/8 1-3/8 the unit corner weight. The unit net weight and shipping weight...
Table 4: Table 4. Minimum Supply Maximum Supply Model Voltage Voltage CPLE090-3 CPLE090-4 CPLE120-3 CPLE120-4 Voltage Balance The supply voltage shall be unbalance (phase Filter Drier and Sight Glass. A bi-flow liquid line filter drier is factory to phase) within 2%.
Page 6
75’. Calculate the minimum wire size assuming no more than 2% voltage drop. CONDENSING UNIT HANDLER AH090/120 CPLE090/120 MCA for CPLE120-3 = 43.3 (from S&R plate and table). GREEN YELLOW ORANGE Applying previous table wire sizes less than #8 AWG cannot be used for circuits which have a rating of 45A.
Page 7
Control Box Components See Figure 10 for the location of the To avoid possible explosion, use refrigerant cylinders properly: electrical components. If you must heat a cylinder for faster charging, partly immerse it in warm water. Never apply flame or steam to the cylinder. Figure 10.
Page 8
PRELIMINARY CHARGE ADJUSTMENT SYSTEM EVACUATION IMPORTANT: Connect the vacuum pump, high vacuum manifold set with See the wiring diagram or outdoor unit specification sheet high vacuum hoses, thermocouple vacuum gauge and to determine if this unit has a crankcase heater. If it does, charging cylinder as shown.
Page 9
For installation greater than 25’ of line set, indoor unit airflow, Allow the system to operate for at least 20 minutes. condensing unit location and number of tubing fittings will have an impact on final unit charge amount. Start with half of the 25’ Attach and insulate an electronic thermometer to the hot gas line set charge and proceed.
0 V (open sensor). 3 Phase Scroll Compressor I. Shut off power to the unit. The CPLE090/120 condenser is equipped with a 3-phase scroll compressor. If the unit sounds noisy and/or the suction J. Replace outdoor fan motor wire removed in Step D.
Page 11
TROUBLESHOOTING ANALYSIS TABLE - COOLING TROUBLE SHOOTING ANALYSIS TABLE COMPLAINT PROBABLE CAUSE REMEDY 1. Purge or pump-down excessive charge. 1. Excessive charge of refrigerant in system. 2. Make certain that coil is not fouled in any 2. Inadequate supply of air across the 1.
Finally, every unit is run tested before it leaves the factory. That’s why we know... There’s No Better Quality. Visit our website at www.goodmanmfg.com for information on: • Goodman products • Warranties • Customer Services •...