Figure 85
(continued) Sola CONFIGURATION VALUES — setup options — White text on black titles are configuration
groups — see Figure 62, page 61 for location of configuration group in menus
Menu/Item
Units
Lead Lag Master Configuration ADVANCED — Modulation tab
(Use scroll arrows to toggle between Central Heat, Domestic Hot Water, Mix, Frost Protection, Outdoor reset,
Warm Weather Shutdown, Algorithms, Rate Allocation, Add Stage, Drop Stage and Modulation pages)
Modulation backup
sensor
Off hysteresis
°F or °C
On hysteresis
°F or °C
P gain
I gain
D gain
86
-
fired water boiler
Low
High
Default
Value
Value
See description
Disabled
2°F
20°F
10°F
(1°C)
(11°C)
(6°C)
2°F
20°F
10°F
(1°C)
(11°C)
(18°C)
Not adjustable
50
Not adjustable
50
Not adjustable
50
— Boiler Manual
(continued)
Description
• Disabled
• Lead boiler outlet sensor
• Slave boiler outlet sensor average
Temperature rise above setpoint where lead lag operation ends.
Temperature drop below setpoint where lead lag operation starts.
Gain adjustment for proportional calculation of load response.
Gain adjustment for integral calculation of load response.
Gain adjustment for differential calculation of load response.