Sola control interface and menus

Power-up & initialization
1. When power is applied, the display loads operating software
and performs self diagnostics. The
Figure 60) will appear when the device is properly powered and
initialization is successful.
a. Select the SETUP button to adjust backlight and sound if
desired.
2. The
stand-by screen
(screen saver showing WEIL-McLAIN
logo) appears if the display is left idle for a time and screen saver
is enabled set in the Display Setup menu (SETUP
SETUP
SCREEN SAVER tab).
3. A
camera icon
on the left top corner is for screen snapshot
use. Up to 16 snapshots can be stored in the display and can be
copied to a USB memory stick. On any screen that displays the
camera icon, press the camera to record the screen image.
Sola page navigation
1. The pages are arranged in a tree structure, as shown in Figure 62,
page 61.
Figure 59
Sola display Home page (Single boiler system
—boiler in normal operation)
Figure 60
Sola display Home page (Boiler #1 in multiple
boiler system —boiler in normal operation)
60
-
fired water boiler
(Figure 59 or
Home page
DISPLAY
— Boiler Manual
Figure 61
The Home page boiler icon will appear
in one of four colors, indicating the boiler
status —
Boiler icon color
PEWTER
— Normal operation
RED
— Lockout condition
YELLOW
— Holding mode (this is a normal
conditions, and indicates that the control is wait-
ing for an event to complete)
BLACK
— Communication error (disconnected
or power off)
Pressing the
control's status page. Control adjustment and
diagnostic pages are accessible from here. See
Figure 62, page 61 for navigation details.
Contractor log-in
1. The installer/technician must log in to change control
settings other than temperature and those settings
available to the user. To log in, press the PADLOCK
button from any setup or configuration screen.
sf
2. Enter this code:
3. After 10 minutes of inactivity, the control will automati-
cally lock again. Log in again using the same procedure
as above.
4. Then hit the enter key. The padlock should now display
as open instead of locked. You must log in again if inac-
tivity time lapses (padlock will show as closed).
5. Hit the padlock again to re-lock the control.
Home page
1. A screen similar to Figure 59 or Figure 60 appears after the display
has completely powered up. The Boiler icon will appear in one of
four colors, indicating the boiler status. See Figure 61.
2. The Home page includes buttons for Lead Lag configuration
when lead lag master or slave in the Sola control is enabled. The
LEAD LAG MASTER button only appears on the master boiler's
home page.
3. Pressing the SETUP button on the Home page displays miscel-
laneous setup and diagnostic functions. It also contains the setup
configuration for building management system applications.
:
BOILER ICON
(
)opens the
(must be lower case)
Part number 550-100-116/0713