Sola control parameter table
Figure 85
(continued) Sola CONFIGURATION VALUES — setup options — White text on black titles are configuration
groups — see Figure 62, page 61 for location of configuration group in menus
Menu/Item
Units
(Use scroll arrows to toggle between Central Heat Pump, Boiler Pump, Domestic Hot Water Pump, System Pump, Auxiliary 1 Pump, and Auxiliary 2 Pump
Central Heat:
Service active
DHW: Demand
DHW: Service
active
Local Lead Lag:
Service active
Frost protection:
Central Heat
Frost protection:
DHW
DHW Pump ADVANCED — Force On tab — Force pump on when:
(Use scroll arrows to toggle between Central Heat Pump, Boiler Pump, Domestic Hot Water Pump, System Pump, Auxiliary 1 Pump, and Auxiliary 2 Pump
Local burner
demand
Lead Lag slave
demand
(Use scroll arrows to toggle between Central Heat Pump, Boiler Pump, Domestic Hot Water Pump, System Pump, Auxiliary 1 Pump, and Auxiliary 2 Pump
Local demand
inhibited for faults
(Use scroll arrows to toggle between System Pump, Boiler Pump, Domestic Hot Water Pump, System Pump, Auxiliary 1 Pump, and Auxiliary 2 Pump pages)
Pump control
Pump output
Overrun time
hr mm ss
Use for local
demands
Part number 550-100-116/0713
-
Low
High
Default
Value
Value
DHW Pump ADVANCED — ON OPTIONS tab
pages)
or
or
or
or
or
or
pages)
or
or
DHW Pump ADVANCED — Miscellaneous tab
pages)
or
Pump Configuration
System Pump main page
Auto or ON
Auto
Pump A, Pump B,
Pump B
Pump C or NONE
0h 0m 0s 18h 0m 0s
0h 0m 0s
or
fired water boiler
(continued)
Description
If DHW is the active service controlling the heating system (has heat
demand AND is in control) then this pump will have normal pump-on
demand.
If DHW is calling for heat then this pump will have normal pump-on
demand. A DHW call-for-heat will operate the pump even if some
other service source (e.g. CH) is actually in control of the boiler on
higher priority.
If DHW is the active service controlling the heating system (has heat
demand AND is in control) then this pump will have normal pump-on
demand.
This pump will respond when LL service is currently the highest priority
service for this slave and the Sola LL master has commanded this slave
Sola to start up and fire.
If CH frost protection is active then this pump will have normal pump-
on demand.
If DHW frost protection is active then this pump will have normal
pump-on demand.
If Local demands are enabled, then when the burner has demand (is
firing or preparing to fire, always local) the output will be forced on.
Example, this feature might be used to open a boiler room air damper
(but does NOT implement airflow safety).
If Sola LL Master demand is enabled, then whenever the master is asking
for heat from any slave, this output will be forced on. Example, this
feature might be used to open a boiler room air damper (but does Not
implement airflow safety).
If the local Sola is disabled (e.g. via the burner switch parameter) or
locked out, inhibit local demand sources (are selected) that might
otherwise request the pump to be on. Otherwise these will run the
pump even though the sola cannot fire.
(continued)
The Pump can be turned on manually, or it can be set to operate
automatically. If it is turned on then it remains on until changed back to
Auto. In Auto mode it operates according to the demand sources listed
above and the overrun time.
This parameter allows the Pump function to be disabled or to activate
any of the three pump outputs on terminal strip D.
This time indicates how long the Pump should remain on after demand
from any source ends. That is, whenever the pump has been on, but the
last requests for the pump to be on ends, it always continues to run for
the time given by this parameter.
Enables pump demand from the local Sola: the one which contains this
pump control block. If not enabled then all local Sola pump demands are
ignored by this pump control block.
— Boiler Manual
HOME PAGE
(Enter changed values in the last column)
CONFIGURATION
Changed
to
77