Electrical Data; Sound Power (Dba) - Carrier 38TXA Product Data

With puron (r-410a) 60 hz sizes 024 thru 060
Hide thumbs Also See for 38TXA:
Table of Contents

Advertisement

Electrical data

OPER VOLTS*
UNIT SIZE-
Max
SERIES
V/PH
024-30
030-30
036-30
208/230/1
253
042-30
048-30
060-31
* Permissible limits of the voltage range at which unit will operate satisfactorily.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed
cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated
(non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used,
consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time-delay fuse.
FLA
— Full Load Amps
LRA
— Locked Rotor Arms
MCA
— Minimum Circuit Amps
RLA
— Rated Load Amps
NOTE: Control circuit is 24-v on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/
compressors contain internal overload protection.
6
COMPR
Min
LRA
RLA
61.0
13.5
72.5
14.7
83.0
15.4
187
105.0
18.6
109.0
20.5
158.0
27.6

SOUND POWER (dBA)

UNIT SIZE-SERIES
024-30
030-30
036-30
042-30
048-30
060-31
60°C
MIN
FAN
WIRE
SIZE†
FLA
MCA
0.8
17.6
14
0.8
19.2
14
1.1
20.2
12
1.1
24.4
10
1.4
27.0
10
1.4
35.9
8
SOUND LEVEL
70
71
71
74
76
78
75°C
60°C
75°C
MIN
MAX
MAX
WIRE
LENGTH
LENGTH
SIZE†
(Ft)‡
(Ft)‡
14
44
42
14
41
39
12
62
59
10
80
76
10
73
70
8
85
80
MAX
FUSE**
OR CKT
BKR AMPS
25
30
30
40
40
60