Problem
A room name cannot
be installed at the
Hometronic Manager.
The
LED illumi-
nates after start-up.
Room controlled
incorrectly.
Cause/Solution
An "*" is already present next to the room in
the "Installation" menu. The room name was
already issued.
Uninstall room name.
For assigning again (see "Assigning zones
and issuing room names" on Page 32).
A fault is present in one of the temperature
zones. See Page 42.
Check wireless connection.
Check cabling for cable break.
Check whether zone is assigned correctly.
Check batteries of the storey controller
and wireless setpoint adjuster.
Check whether adjusting ring of setpoint
adjuster is at position 0.
Check whether adjusting ring can be
turned between –12 and +12 with housing
cover removed.
Check whether or not a setpoint adjuster
is assigned to room.