Table 32; Table 31 Table; Table 33 Rectifier Ac Input (Mains) - Liebert NX User Manual

Nx ups 10-30kva, 400v, 50/60hz
Hide thumbs Also See for NX:
Table of Contents

Advertisement

Technical Specifications

Table 32

Mechanical characteristics
Rated Power, kVA
Dimensions, WxDxH
Mass
Mass without batteries
Finish
Protection Degree, IEC (60529)
Table 33
Rectifier AC input (mains)
Rated Power, kVA
Rated AC Input Voltage
Input Voltage Tolerance
2
Frequency
Power Factor
Input Power
Input Current
Harmonic Current Distortion
Duration of Progressive
Power Walk-In
1. Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.
2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged
battery
3. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charged
4. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.
Unit of
Measurement
mm (in)
kg (lb)
N/A
N/A
Unit of
Measurement
1
VAC
2
VAC
Hz
kW/kVA, full
load
(half load)
3
kVA rated
4
(maximum
)
3
A rated
4
(maximum
)
THDI % FL
sec
74
10
15
600x700x1400
(23-9/16x27-5/8x55)
180 (397)
204 (450)
Pantone 877 (Silver grey)
equivalent Becker Silver epoxy polyester powder 041-37-2
IP20 (finger-proof with front doors open or closed)
10
15
380/400/415
(3-phase and sharing neutral with the bypass input)
305V to 477V
304V to 208V (output derated below 70%)
50/60Hz (tolerance 40Hz to 70Hz)
0.99 (0.98)
8.9 (11.7)
13.3 (18.9)
12.9 (16.9)
19.3 (27.4)
3
3
10 seconds to reach full rated current
(selectable 5 through 30 seconds in 5-second intervals)
20
30
204 (450)
210 (463)
20
30
17.8 (23.3)
26.6 (35.0)
25.8 (33.8)
38.6 (50.7)
3
3