Liebert NX User Manual page 69

Nx ups 10-30kva, 400v, 50/60hz
Hide thumbs Also See for NX:
Table of Contents

Advertisement

Operator Control Panel and Display
Table 22
UPS messages (continued)
Message
Bypass Abnormal
Inverter Asynchronous
Inverter Fault
Inverter Overtemp.
Fan Fault
Inverter STS Fail
Bypass STS Fail
Operation Invalid
Output Fuse Fail
Control Power 2 Fail
Unit Over load
System Over load
Description / Suggested Action (if any)
This alarm is triggered by an inverter software routine when the amplitude or frequency of
bypass voltage exceeds the limit.
This alarm automatically resets once the bypass voltage goes normal.
First check if there are some relevant alarms such as "Bypass disconnect open", "Bypass phase
reverse" and "Mains neutral lost". If they appear, solve them first.
1. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass
limit. Note here the rated voltage and frequency are specified by "Output voltage level" and
"Output frequency level" respectively.
2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and
frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If
the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger
through the configuration software according to the customer's agreement.
This alarm is triggered by an inverter software routine when the inverter and bypass waveforms
are misaligned by more than 6 degrees in phase. This alarm resets automatically once the
condition is no longer true.
1. First check if the alarm "Bypass unable to trace" or "Bypass abnormal" occurs. If so, solve it
first.
2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and
seek any possible measurements.
Inverter output voltage beyond limits. Load transfers to bypass.
The temperature of the inverter heat sink is too high to keep inverter running.
This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter
bridge heat sink.
The UPS will recover automatically after a 5 minute delay from the disappearance of the
overtemperature signal.
If the overtemperature condition is true, then check for and verify:
1. high ambient air temperature.
2. blocked cooling airway.
3. any fan failure.
4. prolonged inverter overload
At least one of the cooling fans has failed
At least one of the static switches of inverter side is open or short circuit. This fault is locked until
power off.
At least one of the static switches of bypass side is open or short circuit. This fault is locked until
power off
This record is registered following an incorrect operation:
At least one of the inverter output fuses is blown. Inverter shuts down. Load transfers to bypass.
UPS operates but Redundant Control Power is not available.
The UPS is confirmed to be overload when the load arises above 105% nominal rating.
The alarm automatically resets once the overload condition is removed.
1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to
determine which phase is being overloaded.
2. If the alarm is true, measure the actual output current to verify that the indications are valid.
Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing
error can also leads to the alarm.
The UPS parallel system is confirmed to overload when the total load arises above 105%
nominal rating for the set basic number of UPSs. The alarm automatically resets once the
overload condition is removed.
1. Confirm that the alarm is true by checking the system load percent indicated on the LCD
panel to determine which phase is being overloaded.
2. If the alarm is true, measure the actual output current to verify that the indications are valid.
Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing
error can also leads to the alarm.
61