TRADELINE
Pilot burners provide main burner ignition for standing pilot natural and LP gas systems. Used with a thermocouple to provide
automatic pilot safety control. Used with a thermopile in a self-powered system. See Table 1 for model specifications.
Primary
Model
Aerated
Q314A
Q327A
WHEN INSTALLING THIS PRODUCT...
1. Read these instructions carefully. Failure to follow
instructions can damage product or cause a hazardous condi-
tion.
2. Check ratings given in instructions and on product to
make sure product is suitable for your application.
3. Make sure installer is a trained, experienced service
technician.
4. After completing installation, use these instructions to
check out product operation.
WARNING
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH
Follow these warnings exactly.
1. Disconnect power supply before wiring to pre-
vent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at appliance service valve
before starting installation and perform Gas
Leak Test after completion of installation.
3. Do not bend pilot tubing at the control or pilot
after compression nut has been tightened. Gas
leakage at the connection may result.
Follow appliance manufacturer's instructions if avail-
able; otherwise, use instructions provided below.
LOCATION
1. Position pilot burner for easy access, observation, and
lighting. In replacement applications, replace pilot burner
TABLE 1—MODEL SPECIFICATIONS.
Type of
Orifice
No
Insert
Yes
Spud
Installation
J. H. • Rev. 12-92 • © Honeywell Inc. 1992 • Form Number 69-0519—3
Q314 and Q327A
Pilot Burners
Pilot Tip
Type
Includes
Target
Includes natural and LP gas orifices, 1/4 in.
compression fitting, "F," "K," or "L" tip styles,
"B" mounting bracket, and "A" mounting bracket
adapter.
Target
Includes natural and LP gas orifices, 1/4 in.
compression fitting, and "B" mounting bracket
with screws.
with an identical unit and position new pilot burner in the
same location and orientation as the original pilot burner.
2. Mount pilot burner on main burner. Mounting surfaces
other than the main burner can shift, bend, or warp as furnace
expands and contracts while operating. See Fig. 1.
3. Mount pilot burner so the ignition flame remains
properly positioned with respect to the main burner flame.
See Fig. 2.
4. Supply pilot flame with ample air free of combustion
products.
5. Do not impinge pilot flame on adjacent parts. Do not
impinge main burner flame on pilot burner.
6. Do not expose pilot flame to falling scale which could
impair ignition of main burner.
7. Do not expose pilot burner to main burner rollout while
igniting or extinguishing.
8. Do not expose pilot flame to drafts that push or pull
pilot flame away from the thermocouple or thermopile.
Fig. 1—Mount pilot burner on main burner.
PILOT
BURNER/GENERATOR
MUST BE RIGIDLY
POSITIONED
RELATIVE TO
MAIN BURNER
Application
M1263

Advertisement

loading

Summary of Contents for Honeywell TRADELINE Q314

  • Page 1 TRADELINE Pilot burners provide main burner ignition for standing pilot natural and LP gas systems. Used with a thermocouple to provide automatic pilot safety control. Used with a thermopile in a self-powered system. See Table 1 for model specifications. Primary...
  • Page 2 2. Push clip into place. See Fig. 6. 3. Insert bleed gas tubing until 3/8 inch [10 mm] of tubing is above pilot burner bracket. Tip of bleed gas tubing must not M3295 extend into pilot flame.
  • Page 3: Startup And Checkout

    4. Insert new compression nut over pilot tubing and slide out of the way. 5. Insert new orifice into pilot burner and push pilot tubing into the pilot burner until it bottoms. 6. While holding tubing all the way in, slide compression fitting into place and engage threads.
  • Page 4 LP systems), soft and steady. See Fig. 9 for examples of possible pilot flame problems and their causes. • If pilot burner is damaged, replace it with an identical pilot burner and mount and position in the same location and orientation.
  • Page 5 PILOT position. NOTE: If using a Honeywell W129A Millivoltmeter, turn the pilot gas adjustment screw until the thermocouple open circuit voltage is 2 mV. Omit steps 2,3, and 4 and proceed with step 5.