External battery pack compatibility
DC system voltage (VDC)
Battery recharge rate (included
batteries)
Replacement battery cartridge
(internal UPS battery replacement)
Battery Access
Battery replacement description
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Undervoltage correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
UPS AC suppression response time
EMI / RFI AC noise suppression
PHYSICAL
Installation form factors supported
with optional accessories
Primary form factor
UPS / Power Module dimensions in
primary form factor (height x width x
depth / inches)
UPS / Power Module dimensions in
primary form factor (height x width x
depth / cm)
Rack Height
Secondary form factor
UPS / Power Module weight (lbs)
UPS / Power Module weight (kg)
BP192V12-3U
192
6 hours from 10% to 90% (internal batteries)
RBC5-192
Front panel battery access door
Hot-swappable, user replaceable internal batteries
Online, double-conversion power conditioning
Corrects overvoltages as high as 300V (<90% load) and 280V (full load)
Corrects undervoltages as low as 100 (<50% load) and 155V (full load); derates linearly
6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel switch
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass
switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without
disrupting power to connected loads
Instantaneous
Yes
2 post rackmount (2POSTRMKITHD); Tower (2-9USTAND)
Rackmount
6.85 x 17.5 x 20.7
17.4 x 44.5 x 52.6
4U
Tower
116.2
52.8
4 / 7