And Height Difference - Fujitsu ASU9RMLQ Manual

Multi type : 3-4 rooms type
Hide thumbs Also See for ASU9RMLQ:
Table of Contents

Advertisement

5. COEFFICIENT OF COMPENSATION FOR PIPE LENGTH

AND HEIGHT DIFFERENCE

This table is created using the maximum capacity.
INDOOR UNIT 9000BTU (AOU36R)
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
COOLING
Indoor unit is upper
than outdoor unit
Height difference H
Indoor unit is under
than outdoor unit
HEATING
Indoor unit is upper
than outdoor unit
Height difference H
Indoor unit is under
than outdoor unit
Indoor unit
Connection pipe
1
Indoor unit is upper than outdoor unit.
15m 49ft.
1
10m 33ft.
7.5m 25ft.
0.991 0.992 0.991 0.984 0.972 0.955
5m
16ft.
0m
0ft. 0.999 1.000 0.999 0.992 0.979 0.963
0.999 1.000 0.999 0.992 0.979 0.963
-5m -16ft.
2
-7.5m -25ft.
-10m -33ft.
-15m -49ft.
15m 49ft.
1
10m 33ft.
7.5m 25ft.
1.018 1.000 0.972 0.936 0.914 0.902
5m
16ft.
0m
0ft. 1.018 1.000 0.972 0.936 0.914 0.902
-5m -16ft.
1.013 0.995 0.967 0.932 0.910 0.898
2
-7.5m -25ft.
-10m -33ft.
-15m -49ft.
Height difference H
H
Outdoor unit
- (02 - 06) -
Pipe length
5m
7.5m
10m
15m
20m
16ft.
25ft.
33ft.
49ft.
66ft.
-
-
-
0.968 0.956 0.940
-
-
0.983 0.976 0.964 0.947
-
0.988 0.987 0.980 0.968 0.951
-
1.000 0.999 0.992 0.979 0.963
-
-
0.999 0.992 0.979 0.963
-
-
-
0.992 0.979 0.963
Pipe length
5m
7.5m
10m
15m
20m
16ft.
25ft.
33ft.
49ft.
66ft.
-
-
-
0.936 0.914 0.902
-
-
0.972 0.936 0.914 0.902
1.000 0.972 0.936 0.914 0.902
-
-
0.993 0.965 0.929 0.907 0.895
0.962 0.927 0.905 0.893
-
-
0.922 0.900
-
-
-
Outdoor unit
H
Connection pipe
2
Indoor unit is under than outdoor unit.
25m
82ft.
25m
82ft.
0.889
Indoor unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents