3. Square off and remove burrs from end of tubing.
4. Use the compression fitting supplied with this gas
control. Slip the fitting over the tubing and slide out of the
way.
NOTE: When replacing a gas control, cut off old compres-
sion fitting and replace with the new compression fitting
provided on the gas control. Never use the old compres-
sion fitting because it may not provide a gas-tight seal.
5. Push tubing into the pilot gas tapping on the outlet end
of the control until it bottoms. While holding tubing all the
way in, slide compression fitting into place, engage threads
and turn until finger tight. Then tighten one more turn with
wrench. Do not overtighten. Refer to Figs. 5 and 6.
6. Connect other end of tubing to pilot burner according
to pilot burner manufacturer instructions.
Fig. 5—Always use new compression fitting.
GAS CONTROL
FITTING BREAKS OFF AND CLINCHES
TUBING AS NUT IS TIGHTENED
WIRING
CAUTION
Disconnect power supply before making wiring
connections to prevent electrical shock or equip-
ment damage.
Follow the wiring instructions furnished by the appliance
manufacturer, if available, or use the following general in-
structions. Where these instructions differ from the appliance
manufacturer, follow the appliance manufacturer instructions.
Fig. 7—Install wire adapter for hot surface or direct spark ignition systems. Pilot plug must be in the
valve pilot opening.
TIGHTEN NUT ONE TURN
BEYOND FINGER TIGHT
TO
BURNER
Fig. 6—Remove pilot gas seal (plug) and
install pilot gas tube for intermittent pilot
application on VR8345.
M3076A
All wiring, including insulated quick connect terminals,
must comply with applicable electrical codes and ordinances.
1. Check the power supply rating on the gas control and
make sure it matches the available supply. Install thermostat
and other controls as required.
2. When the gas control is installed on a hot surface or
direct spark ignition system, attach the wire adapter provided
to the wiring terminals. See Fig. 7 for the wire terminal
location.
3. Connect control circuit to gas control terminals. See
Figs. 3 and 8, 9, or 10.
4. Adjust the thermostat heat anticipator to 0.7, the rating
stamped on the valve operator.
P V
P V
V
M
V
M
PILOT GAS SEAL
(PLUG)
M8440
7
WIRE
ADAPTER
PILOT GAS
TUBE
P V
P V
V
M
V
M
M8441
69-0844—1