5-2. FUNCTION TABLE
No
Control Function Control Objects
1
Initial
Operation
2
Temperature
Control
3
Turbo
Freeze
Buzzer
1. Buzzer will be ring within 2 seconds when you plugged-in and turned
Fan
on the power switch.
Lamp
2. 88 LED displays inside temperature.
88 LED
3. Compressor will be run if evaporator's temperature is higher than
38.3˚F(3.5˚C), compressor will not run for 3 minutes when you
plugged-in.
4. The fluorescent lamp will come on, when the inside temperature has
reached 23˚F(-5˚C).
5. If inside temperature is lower than -50˚F or higher than 50, 88 LED
displays 'Lo' or 'Hi' respectively.
6. Evap. Fan Motor will be run if D-sensor sense lower than 14˚F or 10
minutes has passed from when you plugged-in.
Compressor
1. By pushing up/down button, you can set the desired inside
Evap-Fan Motor
temperature from '5˚F' to '-17˚F'.
Con-Fan Motor
2. 88 LED will display a setting temperature, when you push up/down
LED
button.
3. 88 LED will indicate real inside temperature, after your setting.
4. Buzzer rings 1 time whenever each button is pressed.
5. Compressor automatically turns on and off by F-sensor (Except
error mode)
6. Compressor will not come on for 3 minutes After Compressor is Off,
even though the F-sensor is at On point.
7. Evap. Fan Motor runs continuously except when door is opened and
during defrost mode.
8. Evap. Fan Motor will start within 3 seconds when door is closed.
9. Compressor On/off temperature(˚F)
Setting
Comp On
Comp Off
Setting
Comp On
Comp Off
Setting
Comp On
Comp Off
Setting
Comp On
Comp Off
Setting
Comp On
Comp Off
Compressor
1. If the Turbo Freeze button is pressed, the Turbo freeze mode will
Evap-Fan Motor
start.
Con-Fan Motor
2. If the Turbo Freeze button is pressed during the Turbo Freeze mode,
LED
the Turbo Freeze mode is canceled.
3. During the Turbo Freeze mode, the temperature up/down button will
not operate.
4. T.F lamp in 88 LED is lighted during the Turbo Freeze mode.
5. The compressor and Condenser-Fan Motor operate continuously for
120 minutes.
ELECTRONIC CONTROLLER INSTRUCTION
Contents
5
4
3
9
8
7
1
0
-1
0
-1
-2
4
3
2
-4
-5
-6
-5
-6
-7
-1
-2
-3
-9
-10
-11
-10
-11
-12
-6
-7
-8
-14
-15
-16
-15
-16
-17
-11
-12
-13
-19
-20
-21
91
Remark
2
1
6
5
-2
-3
-3
-4
1
0
-7
-8
-8
-9
-4
-5
-12
-13
-13
-14
-9
-10
-17
-18

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents