Mitsubishi PEH series User Manual page 46

Peh series air-cooled split-type ducted air conditioners, heat pump
Table of Contents

Advertisement

2 2 2 2 2 -7.2. Wiring and fitting capacities
<PUH>
Main power supply wire thickness and switch capacities.
Power supply thickness *1
Overcurrent protector *2
Power supply thickness *1
Overcurrent protector *2
Thickness of wires for remote control-
ler and indoor unit *3
Thickness of wire between indoor and
outdoor unit
Ground wire thickness
Notes:
*1: "Power supply thickness" indicates the thinnest allowable metal wire.
*2: "Overcurrent protector" indications are for when class B fuse are used.
*3: These wires are supplied with optional remote controller and branch pip-
ing.
*4: Power supply codes of parts of appliances for outdoor use shall not be
lighter than polychloroprene sheathed flexible cord (design 245 IEC 57).
*5: A switch with at least 3 mm contact separation in each pole shall be
provided by the Air conditioner installation.
Table above is an example. The selection of other capacities should be deter-
mined in accordance with the relevant standards.
Types of cable/cord
Vinyl cab tire round cord: VCTF
Vinyl insulating vinyl sheath cable round type: VVR
PUH-7, 8
PUH-10
2
mm
8 or more
14 or more
A
50
60
2
mm
2.0
A
15
mm
2
0.8 or more *3
2
mm
1.5 or more
2
mm
8 or more
14 or more
Vinyl cab tire flat cord: VCTFK
Vinyl insulating vinyl sheath cable flat type: VVF
Vinyl insulating vinyl sheath cable for control: CVV
600 V vinyl cab tire cable: VCT
Vinyl insulating vinyl sheath cable for control: CVS
Warning:
Be sure to use specified cables and connect them firmly so that no external
wiring force is exerted on terminal connections. Loose connections may cause
heat or fire.
Caution:
Some installation sites may required installation of an earth leakage
breaker. Failure to install it may result in an electric shock.
Always use an earth leakage breaker and fuse with the specified capac-
ity. Use of a fuse with a capacity larger than that specified, or use of a
piece of wire or copper wire may cause breakdown or fire.
Example
Connecting with PEH-MYB
[Fig. 2 2 2 2 2 -7.2.1]
PUH-7,8
L1 L2 L3 N
A
B C
PE
PUH-10
L1 L2 L3 N
A
B C
PE
A Power supply
B Breaker
- 44 -
D
PEH-7,8
S1 S2 S3
L
S1 S2 S3
1 L2 L3 N
C B A
D
PEH-10
S1 S2 S3
L
S1 S2 S3
1 L2 L3 N
C B A
C Switch box
D Remote controller
PE
PE