Mitsubishi PEH-rp8 Installation Manual
Mitsubishi PEH-rp8 Installation Manual

Mitsubishi PEH-rp8 Installation Manual

Indoor unit

Advertisement

Quick Links

Air-Conditioners
INDOOR UNIT
PEH-RP8, 10MYA
FOR INSTALLER
FÜR INSTALLATEURE
POUR L'INSTALLATEUR
PARA EL INSTALADOR
PER L'INSTALLATORE
VOOR DE INSTALLATEUR

INSTALLATION MANUAL

For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d'aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
INSTALLATIONSMANUAL
Läs denna installationsmanual noga för säkert och korrekt bruk innan luftkonditioneringen installeras.
INSTALLATIONSMANUAL
Læs venligst denne installationsmanual grundigt, før De installerer airconditionanlægget, af hensyn til sikker og korrekt anvendelse.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
E°XEIPI¢IO O¢H°IøN E°KATA™TA™H™
°È· ·ÛÊ¿ÏÂÈ· Î·È ÛˆÛÙ‹ ¯Ú‹ÛË, ·Ú·Î·Ï›ÛÙ ‰È·‚¿ÛÂÙ ÚÔÛ¯ÙÈο ·˘Ùfi ÙÔ ÂÁ¯ÂÈÚ›‰ÈÔ ÂÁηٿÛÙ·Û˘ ÚÈÓ ·Ú¯›ÛÂÙ ÙËÓ
ÂÁηٿÛÙ·ÛË Ù˘ ÌÔÓ¿‰·˜ ÎÏÈÌ·ÙÈÛÌÔ‡.
MONTAJ ELK‹TABI
Emniyetli ve do¤ru biçimde nas›l kullan›laca¤›n› ö¤renmek için lütfen klima cihaz›n› monte etmeden önce bu elkitab›n› dikkatle okuyunuz.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по
установке до выполнения установки кондиционера.
FÖR INSTALLATÖREN
TIL MONTØREN
PARA O INSTALADOR
°π∞ ∆√¡ ∆∂áπ∫√ ∂°∫∞∆∞™∆∞™∏™
TES‹SATÇININ D‹KKAT‹NE
ДЛЯ СПЕЦИАЛИСТА ПО МОНТАЖУ

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PEH-rp8 and is the answer not in the manual?

Questions and answers

Summary of Contents for Mitsubishi PEH-rp8

  • Page 1: Installation Manual

    Air-Conditioners INDOOR UNIT PEH-RP8, 10MYA FOR INSTALLER FÖR INSTALLATÖREN FÜR INSTALLATEURE TIL MONTØREN POUR L’INSTALLATEUR PARA O INSTALADOR PARA EL INSTALADOR °π∞ ∆√¡ ∆∂áπ∫√ ∂°∫∞∆∞™∆∞™∏™ PER L’INSTALLATORE TES‹SATÇININ D‹KKAT‹NE VOOR DE INSTALLATEUR ДЛЯ СПЕЦИАЛИСТА ПО МОНТАЖУ INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
  • Page 2 [Fig. 2.0.1] A Air outlet B Remote controller C Joint pipe for R410A (Field piping connection) * In case of PEH-RP8 only [Fig. 3.2.1] [Fig. 3.2.2] PEH-RP10: 1580 PEH-RP8: 1380 PEH-RP10: 1480 PEH-RP8: 1280 PEH-RP10: 1440 PEH-RP8: 1240 PEH-RP10: 1480...
  • Page 3 C Gas pipe D Liquid pipe E Service port F Indoor unit G Outdoor unit H Joint pipe (Accessory part ) * Only for PEH-RP8 when connecting to R410A outdoor unit [Fig.7.2.1] A Insulator B Drain pipe Rc1 C Drain pan >...
  • Page 4 B PEH-RP8: 8 × 130pitch = 1040 PEH-RP8 : 31 PEH-RP10: 9 × 130pitch = 1170 C PEH-RP8: 24-ø3 holes (Inlet duct mount holes) PEH-RP10: 26-ø3 holes (Inlet duct mount holes) D Top of the unit E Outlet duct flange F PEH-RP8,10: 7 ×...
  • Page 5 [Fig.9.4.2] [Fig.9.4.3] 1Hr. ON OFF ˚C CLOCK CLOCK FILTER ˚C CHECK MODE STAND BY INDOOR UNIT FUNCTION DEFROST ADDRESS NO 1Hr. ON OFF ˚C CLOCK CLOCK FILTER ˚C CHECK MODE STAND BY INDOOR UNIT FUNCTION DEFROST ADDRESS NO (a) Outdoor unit (b) Indoor unit 1Hr.
  • Page 6 [Fig.10.0.1] [Fig.10.0.2] S1 S2 S3 3ø4W 3ø4W S1 S2 S3 A Indoor unit B Power cable wiring C Control cable wiring D Outdoor unit A Power supply E Breaker F Fuse B Main switch/fuse (purchased locally) G Power cable terminal bed H Control cable terminal bed C Power supply wiring for outdoor unit I Defrost signal cable terminal bed...
  • Page 7 11.4 11.3 [Fig.11.3.1] [Fig.11.4.1] 1Hr. 1Hr. ON OFF ˚C ON OFF ˚C CHECK CLOCK CLOCK FILTER CLOCK FILTER ˚C CHECK MODE ˚C CHECK MODE STAND BY INDOOR UNIT FUNCTION STAND BY INDOOR UNIT DEFROST ADDRESS NO FUNCTION DEFROST ADDRESS NO I Electric current marker 1Hr.
  • Page 8 12.2 12.3 14.1 [Fig.12.2.1] [Fig.12.3.1] [Fig.14.1.1] CHECK TEST RUN ON/OFF TEMP ON/OFF TEMP AUTO STOP AUTO STOP MODE VANE AUTO START MODE VANE AUTO START CHECK LOUVER CHECK LOUVER TEST RUN TEST RUN A Outdoor unit RESET CLOCK B Indoor unit RESET CLOCK E SW 1 - 3 ~ 6...
  • Page 9: Table Of Contents

    - If the pressure switch, thermal switch, or other protection device is shorted electric shock, or fire may result. and operated forcibly, or parts other than those specified by Mitsubishi Elec- • Install the unit at a place that can withstand its weight.
  • Page 10: Precautions For Devices That Use R410A Refrigerant

    2. Indoor unit accessories The unit is provided with the following accessories: <Accessory part position> A Air outlet B Remote controller [Fig. 2.0.1] (P.2) C Joint pipe for R410A (Field piping connection) * In case of PEH-RP8 only...
  • Page 11: Selecting An Installation Site

    3. Selecting an installation site • Select a site with sturdy fixed surface sufficiently durable against the weight of 3.2. Securing installation and service space unit. • Select the optimum direction of supply airflow according to the configuration of • Before installing unit, the routing to carry in unit to the installation site should the room and the installation position.
  • Page 12: Confirming The Unit's Position And Fixing Hanging Bolts

    Take care to ensure H Joint pipe (Accessory part ) that the flame does not come into contact with the main body itself. * Only for PEH-RP8 when connecting to R410A outdoor unit Caution: •...
  • Page 13: Drain Piping Work

    PEH-RP10: 9 × 130pitch = 1170 • To connect the air conditioner main body and the duct for potential equali- C PEH-RP8: 24-ø3 holes (Inlet duct mount holes) zation. PEH-RP10: 26-ø3 holes (Inlet duct mount holes) D Top of the unit •...
  • Page 14: Connecting Procedures

    (3) Install the lower case in the switch box or on the wall. 9.4. Function settings [Fig. 9.1.1] (P.4) (1) Wired type <A> For installation in the switch box [Fig. 9.4.1] (P.4) C Switch box for two pieces D Remote controller cord ⁄...
  • Page 15 Complete function selection If [--] appears in the room temperature display as the mode/setting number, or Press the FILTER A and TEST RUN B buttons simultaneously for at least two if a flashing [88] display appears, a transmission problem may have occurred. Check to see if there is some source of transmission interference (noise) nearby.
  • Page 16: Electrical Wiring

    30 mA 0.1s or less power supply when servicing. And do not touch the S1, S2, S3 terminals NV is a product name of MITSUBISHI. when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-potes type.
  • Page 17: Test Run

    • Switching the external static pressure (PEH-RP8, 10MYA ONLY) [Fig. 10.0.4] (P.6) The unit has been set at the factory so that the standard amount of air is A White connector (50 Pa) C01 B Red connector (150 Pa) C02 provided when the static pressure outside the unit is 50 Pa.
  • Page 18: Self-Diagnosis

    Press the remote controller’s “CHECK” button twice consecutively to be able to run a self diagnosis. See the chart below for content of error code displays. Nonconformity Content Nonconformity Content Nonconformity Content Suction sensor error Tube temperature error E6 ~ EF Signal error between indoor and outdoor Tubing (liquid) sensor error Tube (2-phase tube) sensor error...
  • Page 19: Test Run [For Wireless Remote Controller]

    12. Test run [for wireless remote controller] 12.1. Before test run 12.2. Self-check [Fig. 12.2.1] (P.8) s s s s s After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power sup- 1 Turn on the power.
  • Page 20: Test Run Method

    12.3. Test run method 5 Press the button and check whether fan speed changes. [Fig. 12.3.1] (P.8) VANE 6 Press the button and check whether the auto vane operates prop- 1 Turn on the power to the unit at least 12 hours before the test run. erly.
  • Page 21: The Following Occurrences Are Not Problems Or Errors

    Indoor unit Outdoor unit system address power supply unit PEH-RP8·10MYA – * Set the refrigerant system address of one outdoor unit to 00 for the power supply to the remote controller. (The refrigerant system address is set to 00 when shipped from the factory.)
  • Page 22 EU regulations: 336/EEC Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN WT04436X01 Printed in Malaysia...