1-4 Compaq UPS R3000 XR Maintenance and Service Guide
Figure 1-1. Checking the battery recharge date label
IMPORTANT: Do not use the batteries if the recharge date has passed (Figure 1-1). If the date on the
Battery Recharge Date Label has passed without the batteries being recharged, contact an Authorized
Compaq Service Representative.
IMPORTANT: Compaq recommends that you do not maintain an inventory of spare batteries on-site
unless you implement a procedure to keep these batteries charged while in storage.

Remote Emergency Power Off (REPO)

If the UPS R3000 XR is to be installed in a computer equipment room, it must be connected to a
Remote Emergency Power Off (REPO) circuit. The UPS R3000 XR REPO port is designed to
meet the requirements stated in National Electrical Code (NFPA 70) Article 645-10 and 11 in
North America or the equivalent local and/or national wiring regulations.
THIS PRODUCT CONTAINS
A NONSPILLABLE BATTERY
Next Recharge Date:
14-DEC-01
Please refer to Maintenance Section
of Owner's Manual enclosed inside
Do not dispose of used batteries with general office or household waste.
Return the used battery for proper disposal to:
Compaq, your authorized Compaq Partners, or their agents
A recycling center that meets all local environmental standards
Pb
WARNING: To reduce risk of personal injury or damage to equipment:
Only a licensed electrician can wire the REPO port.
Verify that the main breaker switch is in the OFF position before wiring the REPO port.
In North America, the REPO circuit must comply with the NEC (NFPA 70, Article 725) for a
Class 2 circuit. The REPO port wiring must also meet all other national and local standards
in the area in which it is installed.