EDUS04-906
WARNING
• During pump-down, stop the compressor before removing the refrigerant piping.
pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormally high pressure which could lead to equipment damage or and personal injury.
• During installation, attach the refrigerant piping securely before running the compressor.
open during pump-down, air will be sucked in when the compressor is run, causing abnormally high pressure which could lead to equipment damage and personal injury.
• Be sure to install a ground fault circuit interrupter breaker.
Failure to install a ground fault circuit interrupter breaker may result in electrically shocks, or fire personal injury.
CAUTION
• Do not install the air conditioner where gas leakage would be exposed to open flames.
If the gas leaks and builds up around the unit, it may catch fire.
• Establish drain piping according to the instructions of this manual.
• Tighten the flare nut according to the specified torque. A torque wrench should be used.
If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
Accessories supplied
with the outdoor unit:
Precautions for Selecting the Location
1) Choose a place strong enough to bear the weight and vibration of the unit, The location should not amplified the unit noise.
2) Choose a location where the hot air discharged from the unit and the operationing noise will not be a nuisance to the neighbors.
3) Avoid noise sensitive locations such as bedrooms to avoid future problems.
4) There must be sufficient clearance for carrying the unit into and out of the site.
5) There must be sufficient space around the air inlet and the air outlet with no obstructions to airflow.
6) The surrounding area must be free from the possibility of flammable gas leakage.
7) Install units, power cords and inter-connecting cables at least 10 feet (3m) away from television and radio
sets. This is to prevent interference to images and sounds. (Noises may be heard even if they are more
than 10 feet (3m) away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Do not place moisture sensitive equipment or articles under the outdoor unit condenstate drain.
NOTE: Do not install unit by hanging from a ceiling or stacking units.
CAUTION
When operating the air conditioner in a outdoor temperature
below, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
2) Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.
3) To prevent exposure to wind, it is recommended to install a
baffle plate on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the
snow will not affect the unit.
Room Air Conditioners H-Series
Safety Precautions (2)
Accessories
(A) Installation manual
(C) Binding band
If the compressor is still running and the stop valve is open during
If the compressor is not attached and the stop valve is
Inadequate piping may cause water damage.
(B) Drain plug (Heat pump-Models)
1
There is on the
1
bottom packing case.
Construct a large canopy.
Construct a pedestal.
Install the unit high enough off the
ground to prevent burying in snow.