Flue Installation; Ø60/100Mm Telescopic Flue Kit; Ø60Mm Plume Management Kit; Adjusting The Standard Terminal Length - Worcester GREENSTAR 30CDi Installation, Commissioning And Servicing Instructions

Greenstar cdi classic regular wall hung rsf gas fired condensing regular boiler, for open vented and sealed central heating systems and indirect domestic hot water
Table of Contents

Advertisement

INSTALLATION
4.5

FLUE INSTALLATION

HORIZONTAL FLUE
(60/100mm diameter)
For vertical flues and 80/125mm horizontal flues, please refer to
separate Flue Kit instructions.
Apply silicone lubricant to the sealing surfaces of the
flue components to ease assembly of flue components.
Edge of
case
220 mm
Fig. 28
4.5.1 Ø60/100MM TELESCOPIC FLUE KIT:
Standard telescopic flue 350 - 570mm,
part Number: 7 716 191 082
Longer Telescopic flue 570 - 790mm,
part number: 7 716 191 171
The standard telescopic flue terminal length can be reduced or extended
to within 350 to 570 mm or 570 to 790mm for the longer telescopic flue
without cutting and can be used with Condensfit II flue extension
components.
The terminal end of the standard telescopic flue can be further reduced
to 130mm, if necessary, refer to the Flue Instruction manual
supplied.The plume deflector can be adjusted to redirect the flue
discharge allowing some plume management control, alternatively, a
complete plume management system can be fitted to the flue terminal.
Refer to the Flue Instruction manual supplied with the flue kit.
350mm to 570mm
Min . 130mm cut length
Fig. 29 Telescopic flue
4.5.2 Ø60MM PLUME MANAGEMENT KIT:
Part Number: 7-716-191-086
The plume management system connects to the terminal outlet of the
Telescopic flue and must not be used with the flue terminal of the
Standard Flue Kit.
The plume management system can be reduced by cutting (min
500mm) and can be used with plume management extension
components.
22
WALL
85 mm
Fig. 30
Ø60mm PLUME MANAGEMENT KIT (7-716-191-086) replaces the
plume deflector in the Ø60/100mm telescopic flue terminal.

4.5.3 ADJUSTING THE STANDARD TERMINAL LENGTH:

1. Extend tube (1) by withdrawing from tube (2) to achieve the flue
6720647361-13.1Wo
Fig. 31 Standard telescopic flue
Reducing the standard terminal length:
2. Remove securing screws (3) to detach the terminal assembly from
3. Mark the length required for the terminal (6) as shown (min 130mm)
Plume deflector
6720647361-14.1Wo
Fig. 32 Reducing the standard terminal
L
570 mm
350 mm
2
length required, 350- 570mm for the standard telescopic flue or 570
to 790mm for the longer telescopic flue. Secure with screw provided
and seal joint with the aluminium tape supplied.
L
570 mm
350 mm
2
the turret. Slide terminal section (2) from the terminal assembly and
discard. To use terminal (1) without cutting remove the location lug
(4) on the inner flue tube (5) and remove any burrs. To reduce the
terminal length further:
and cut square, taking care not to damage the tubes.
Remove any burrs and chamfer the outer edge of the tubes to assist
ease of connection and prevent seal damage.
The aluminium tape is not required when reducing the
terminal.
3
2
1
6720643895-30.1Wo
1
6720643895-30.1Wo
1
6720643895-31.1Wo
6 720 806 548 (2013/02)