Boiler Location & Clearances - Worcester GREENSTAR 30CDi Installation, Commissioning And Servicing Instructions

Greenstar cdi classic regular wall hung rsf gas fired condensing regular boiler, for open vented and sealed central heating systems and indirect domestic hot water
Table of Contents

Advertisement

PRE-INSTALLATION
Minimum hole size for the condensate soak away must be
400mm deep by 300mmØ .
In situations where there are likely to be extremes of temperature or
exposure, the use of a proprietary trace-heating system for external pipe
work, incorporating an external frost thermostat, should be considered.
If such a system is used, the requirement to use 32mm pipe does not
apply. However, all other guidance above and the instructions for the
trace heating system, should be closely followed.
NOTICE: Unheated internal areas.
▶ Internal pipe runs in unheated areas such as lofts,
basements and garages should be treated as external
runs.
*
1
500mm min.
13
14
9
11
12
Fig. 15 Soak away
14
*
1
7
Fig. 16 Condensate pump to external disposal
3.5
BOILER LOCATION & CLEARANCES
This boiler is only suitable for installing internally within a property at a
suitable location onto a fixed, rigid non-combustible surface at least the
same size as the boiler and capable of supporting the boiler weight.
NOTICE:
No surface protection is required against heat transfer
from the boiler.
COMPARTMENTS:
Follow the requirements of BS6798 and BS5440 Part 2 and note:
12
• Minimum clearances must be maintained
• An access door is required to install, service and maintain the boiler
and any ancillary equipment.
• If an airing cupboard is adapted to house a boiler, then the airing
spaces must be separated from the boiler compartment by a
noncombustible partition. The partition may be perforated, if
required, by holes not exceeding 13 mm in diameter.
• If the appliance is fitted into a cupboard or a compartment is built
around the appliance after installation, then the compartment must
be built or lined by a non-combustible material.
BOILER CLEARANCES:
The diagram opposite shows the minimum space required to install and
service the boiler.
VENTILATION
This is a room sealed appliance and does not require any air for
combustion from inside the property.
The requirements of BS 6798 and BS 5440 regarding ventilation do not
apply, with the Greenstar CDi Regular boiler. There is no need for
9
ventilation openings to be provided in the compartment because of the
low heat loss from the appliance casing, if the clearances shown are
10
maintained.
Do not operate the appliance if the flue terminal fitted on the outside wall
or roof is obstructed or damaged.
25mm min.
400mm
min.
10
13
*
**
25mm min.
***
Table 5 Minimum clearances
6720644744-12.2Wo
960mm
20mm*
600mm**
5mm
450mm
Minimum clearance to removable door
Minimum clearance required for servicing
Height for either 60/100 or 80/125 flue
5mm
200mm
380mm
6 720 806 548 (2013/02)