Clearances - Heatilator B-Vent Gas Appliance CB4236MIR Owner's Manual

B-vent gas appliance
Table of Contents

Advertisement

C. Clearances
WARNING! Risk of Fire! Maintain specifi ed air space
clearances to appliance and vent pipe:
Insulation and other materials must be secured to
prevent accidental contact.
The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and
making contact with fi replace or chimney.
Failure to maintain airspace may cause overheating and
a fi re.
Note: The appliance must be raised 1 1/4 in. (32 mm) off fl oor so
the Harbor System can be used. Adjust framing and vent locations
accordingly.
1/2 in. (13 mm)
Combustible flooring may be installed
next to the front of the appliance.
30 in.
(762 mm)
clearance to ceiling
36 in.
(914 mm)
Figure 5.2
Clearances to Combustibles
1/2 in.
(13 mm)
Drywall
0 in.
0 (Clearance to
Standoffs)
0 in.
Model
CB4236MIR
in.
mm
CB4842MIR
in.
mm
Heatilator • Caliber Mesh BV Series • 4040-848 Rev G • 10/08
NOTICE: Install appliance on hard metal or wood surfaces
extending full width and depth. DO NOT install directly on
carpeting, vinyl, tile or any combustible material other than
wood.
Note: If the inside of the framed cavity is to be fi nished,
the framing dimensions must include the fi nished surface.
Example: If drywall is to be attached to the rear wall, the
depth must be measured from the drywall surface.
Note: All pipe clearance
specifications are per vent
manufacturer's installation
instructions.
B
C
A
A
B
Rough Opening
Rough Opening
(Width)
(Height)
42
38-3/4
1067
984
48
38-3/4
1219
984
Per Vent
Manufacturer's
Specifications
C
Rough Opening
(Depth)
23-1/2
597
23-1/2
597
19