Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
Name
Default
Schedule options
1
TOD/Economizer
0
output
(terminal A)
Heat fan
0
operation
Reversing value
0
O/B
CPH 1st stage
3
(2)
compressor
CPH 2nd stage
3
(2)
compressor
CPH 1st stage
5
conventional
(2)
heat
CPH 2nd stage
9
conventional
(2)
heat
CPH for auxiliary
9
(2)
heat
CPH for
9
emergency
(2)
heat
Continuous
0
backlight
Changeover
1
(3)
Deadband
3
Minimum
5
compressor off
time
Power supply
0
frequency
Temperature
0
sensor selection
Opts.
Descriptions
0
Non-programmable
1
Programmable
0
Unused
1
TOD energizes terminal A during occupied period, not during
unoccupied period.
2
Economizer energizes terminal A during a call for cool
0
System controls fan
1
Thermostat controls fan
0
O/B terminal energized in cooling
1
O/B terminal energized in heating
1-5
Cycles per hour for 1st stage compressor - only for systems with cool or heat
pump stage - also changes 2nd stage cool default CPH
1-5
Cycles per hour for 2nd stage compressor - only for systems with two cool or
heat pump stages
1-10
Cycles per hour for 1st stage conventional heat - only for systems with heat
stages - also changes 2nd stage heat default CPH
1-10
Cycles per hour for 2nd stage conventional heat - only for systems with two
conventional heat stages
1-10
Cycles per hour for auxiliary heat - only for heat pump systems with more
heat than cool stages
1-10
Cycles per hour for emergency heat - only for heat pump systems with more
heat than cool stages
0
Backlight "ON" time is limited
1
Backlight does not turn off
0
Manual changeover (heat/cool/off) - manually changeover the thermostat
between heat, cool, and off
1
Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover
2
2° F (1° C)
3
3° F (1.5° C)
4
4° F (2.0° C)
5
5° F (2.5° C)
6
6° F (3.0° C)
7
7° F (3.5° C)
8
8° F (4.0° C)
9
9° F (4.5° C)
0-5
Minutes for compressor off time - for systems with cool or heat pump stages
- (Minutes specified here are added to the 5 min base off time.)
0
60Hz
1
50 Hz
0
Internal for H/C - display can show only local temperature and setpoint
1
Internal for H/C - remote (connected to S1 & S2)
show local and remote temperature, and setpoint
2
Internal for H/C, remote (connected to S1 & S2)
auxiliary lockout; display can show local and remote temperature, and
setpoint - (Disabled for conventional systems.)
3
Remote (connected to S1 & S2)
remote indoor temperature and setpoint
(4)
for display - display can
(4)
for compressor and
(4)
for H/C, internal disabled; display can show
BAS-SVX36C-EN