PGM Output Option [01], [03] to [08], [11] to [22], [25]
Option
Description
[3]
ON: the PGM output will operate normally (switch to ground when activated). OFF: the PGM output will be normally ground and switch
to open collector (open circuit) when activated.
PGM Output Option [19] to [22]
Option
Description
[4]
ON: the PGM output will activate for the duration of the PGM Output Timer when the [ ][7][x] command is performed.
OFF: the PGM output will latch until the [ ][7][x] command is performed again.
[5]
ON: a valid user code must be entered after the [ ][7][x] command. OFF: user code is not required.
PGM Output Option [09]
Option
Description
[1]
ON: PGM output activates if a Service Required trouble condition is present.
[2]
ON: PGM output activates if an AC trouble condition is present.
[3]
ON: PGM output activates if a Telephone Line trouble condition is present.
[4]
ON: PGM output activates if a Failure to Communicate trouble condition is present.
[5]
ON: PGM output activates if a Zone Fault condition is present.
[6]
ON: PGM output activates if a Zone Tamper condition is present.
[7]
ON: PGM output will activates if a Wireless Low Battery trouble condition is present.
[8]
ON: PGM output will activates if a Loss of Clock trouble condition is present.
PGM Output Option [10]
Option
Description
[1]
ON: PGM output activates if a Burglary Alarm occurs.
[2]
ON: PGM output activates if a Fire Alarm occurs.
[3]
ON: PGM output activates if a Panic Alarm occurs.
[4]
ON: PGM output activates if a Medical Alarm occurs.
[5]
ON: PGM output activates if a Supervisory Alarm occurs.
[6]
ON: PGM output activates if a Priority Alarm occurs.
[7]
ON: PGM output will activates if a 24-Hour Hold-Up Alarm occurs.
[8]
ON: the PGM output activates for the time programmed for the PGM Output Timer. OFF: the PGM output will latch until a valid user
code is entered.
If System Event PGM is programmed to follow the command output timer then all attributes must be enabled.
Section [551] to [564] PGM Partition Assignment
These sections are used to customize the operation of the PGM outputs (Section [551] for PGM 1, Section [552] for PGM 2 etc.). Turn on the
correct option in the correct section to assign the PGM output to a specified partition. PGM outputs can be assigned to more than one parti-
tion. For PGM outputs that are considered 'system' outputs (e.g.,Trouble output), programming in these sections will not affect the opera-
tion of the PGM output.
Section [700] Automatic Clock Adjust
Program the number of seconds for the last minute of the day. This can be used to make minor corrections to the clock if the AC frequency
is not reliable. Valid entries are [01] to [99].