3=3. PIPE CONNECTION
Fasten flare nut with a torque wrench as specified in the table above.
When fastened too tight, flare nut may eventually break and cause refrigerant
leakage.
indoor
unit connection
Connect both liquid and gas piping to indoor unit.
• Apply a thin coat of refrigerant oil (J) on the seat surface of pipe.
To connect, first align the center, then tighten the first 3 to 4 turns of flare nut.
Use tightening torque table in (3-2.) as a guideline for indoor unit side joints, and tighten
using two wrenches. Excessive tightening damages
the flare section.
Outdoor
unit connection
Connect
pipes to stop valve pipe joint of the outdoor
unit following
the same procedure
detailed in Indoor unit connection.
For tightening,
use a torque wrench or spanner.
3-4. INSULATION AND TAPING
t) Cover piping joints with pipe cover.
2) For outdoor unit side, insulate the piping, including valves.
3) Apply piping tape (G) starting from the connection
on the outdoor unit.
• When piping has to be installed through a ceiling, closet or where the temperature
and
humidity are high, use additional field-supplied
insulation to prevent condensation.
4-1. PURGING
PROCEDURES
AND LEAK TEST
1) Remove service port cap of stop valve on the side of the outdoor
unit gas pipe. (The
stop valves are fully closed and covered in caps in initial state.)
2) Connect gauge manifold
valve and vacuum pump to service port of stop valve on the
gas pipe side of the outdoor unit.
3) Run the vacuum pump 15 minutes or more.
4) Check the vacuum with the gauge manifold valve, then close it and shut off the vacuum
pump.
5) Leave as it is for one or two minutes.
Make sure pointer gauge manifold valve remains
in the same position.
Confirm that pressure
gauge
shows
0.101 MPa [Gauge] ( 30
in.Hg [-760 mmHg]).
6) Quickly remove gauge manifold valve from service port of stop valve.
7) After refrigerant
pipes are connected
and evacuated,
fully open all stop valves on both
sides of gas pipe and liquid pipe. Operating
the unit without fully opening
the valves
lowers the performance
and causes problems.
8) Refer to t-3.
SPECIFICATIONS,
and charge
the prescribed
amount
of refrigerant
if
needed. Be sure to charge slowly with liquid refrigerant.
Otherwise,
composition
of the
refrigerant in the system may be changed and affect performance
of the air conditioner.
9) Tighten cap of service port.
10) Conduct a leak test
*4 to 5 turns
*Close
*Open _-*
Hexagonal wrench
Stop valve cap
0.101 MPa
Compound
pressure gauge
(Torque 19.6 to
(-30 in.Hg
(for R410A)
29.4 N,m. 15 to
[ 760 mmHg])
Pressure gauge
22 Ibfoft [200 to Stop valve
€' (for R410A)
300 kgf-cm])
for LIQUID
Gauge manifold valve
Handle
(for R410A)
Low
Stop valve for
Service
port cap
(Torque 13.7 to
Adapter for pre-
17.7 N,m, 10 to 13
venting the back
Ibf,ft [140 to 180
flow
kgf,cm])
Handle High
e hose
(for R410A)
Vacuum
pump (or the vacuum
pump with the function to
prevent
the back flow)
-Precautions
when usin
the control valve] When
attachinq
the control
valve
to the service port, valve core may
seClose
\
g
Body
deform or loosen if excess pressure
is applied. This may cause qas leak.
When attaching
the control valve to
the service port, make sure that the
valve core is in closed position, and
then tighten
part A. Do not tighten
part A or turn the body when valve
core is in open position.
4=2. TEST RUN
_.
1) Insert power supply plug into the power outlet and/or turn on
the breaker.
2) Press the E.O. SW once. Test run will be performed
for 30
minutes.
If the left operation
indicator
light blinks every 0.5
seconds,
inspect the indoor/outdoor
unit connecting
wire
(A). After the test run, emergency
COOL mode (75°F [24°C]
.....................
COOL) will start.
3) To stop operation,
press the E.O. SW several times until all
LED lamps turn off. Refer to operating
instructions
for de-
tails.
\ Emergency
operation switch
(E.O. SW)
Checking the remote (infrared) signal reception
Press the ON/OFF
button on the remote controller
and listen for an audible indicator from
the indoor unit. Press the ON/OFF
button again to turn the air conditioner
off.
Once the compressor
stops, the restart preventive
device operates so the compressor
will not operate for 3 minutes to protect the air conditioner.
4-3. AUTO RESTART FUNCTION
This product is equipped
with an auto restart function.
When the power supply is cut off
during operation,
such as during blackouts,
the function automatically
starts operation
in
the previous setting once the power supply is resumed. (Refer to the operating instructions
for details.)
Caution:
• After test run or remote signal reception
check, turn off the unit with the E.O. SW
or the remote controller
before turning off the power supply. If this procedure
is
not performed,
the unit will automatically
begin operation
when power supply is
resumed.
To the user
• After installing the unit, explain to the user about auto restart function.
If auto restart function is unnecessary,
it can be deactivated.
Consult the service
representative
to deactivate the function. Refer to the service manual for details.
4=4. EXPLANATION
TO THE USER
Using the OPERATING
INSTRUCTIONS,
explain
to the user how to use the air
conditioner
(the remote controller, removing the air filters, placing or removing the re-
mote controller from the remote controller
holder, cleaning methods,
precautions for
operation,
etc.)
Recommend
that the user read the OPERATING
INSTRUCTIONS
carefully.