Location Relative To Cooling Equipment; Air For Combustion And Ventilation; Personal Injury/Property Damage/Fire/Furnace Corrosion Hazards; Installation In A Garage Diagram - Payne PG8MAA Installation And Operating Instructions Manual

Series 140/e single-stage deluxe, induced-combustion 4-way multipurpose gas furnace
Table of Contents

Advertisement

PERSONAL
INJURY A ND/OR P ROPERTY
DAMAGE H AZARD
Failure
to follow
this
caution
may
result
in
furnace
component
damage.
This gas furnace
may be used for heating
buildings
under
construction
provided
that:
-The
furnace
is permanently
installed
with
all electrical
wiring,
piping,
venting
and ducting
installed
according
to
these installation
instructions.
A return air duct is provided,
sealed
to the furnace
casing,
and terminated
outside
the
space
containing
the
furnace.
This
prevents
a negative
pressure
condition
as created
by the circulating
air blower,
causing
a
flame
rollout
and/or
drawing
combustion
products
into the structure.
-The
furnace
is controlled
by a thermostat.
It may not be
hot wired
to provide
heat
continuously
to the
structure
without
thermostatic
control.
-Clean
outside
air is provided
for combustion.
This
is to
nfininfize
the
corrosive
effects
of adhesives,
sealers
and
other
construction
materials.
It
also
prevents
the
entrainment
of drywall
dust into combustion
air, which can
cause fouling
and plugging
of furnace
components.
-The
temperature
of the
return
air
to
the
furnace
is
maintained
between
55°F
(13°C)
and 80°F
(27°C),
with
no evening
setback
or shutdown.
The use of the furnace
while
the structure
is under
construction
is deemed
to be
intermittent
operation
per our installation
instructions.
-The
air temperature
rise is within
the rated rise range on
the furnace
rating
plate, and the gas input rate has been set
to the nameplate
value.
-The
filters
used
to clean
the
circulating
air during
the
construction
process
must be either changed
or thoroughly
cleaned
prior to occupancy.
-The furnace,
ductwork
and filters are cleaned
as necessary
to remove
drywall
dust
and construction
debris
from
all
HVAC system
components
after construction
is completed.
-Verify
proper
furnace
operating
conditions
including
ignition,
gas input
rate, air temperature
rise, and venting
according
to these installation
instructions.
FIRE
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury,
death and/or property
damage.
Do not install the furnace
on its back or hang furnace
with
control
compartment
facing
downward.
Safety
control
operation
will
be
adversely
affected.
Never
connect
return-air
ducts to the back of the furnace.
(See Fig. 60
BACK
J
A
Fig. 6 -
Prohibit
Installation
on Back
A02054
LOCATION
RELATIVE
TO COOLING
EQUIPMENT
The
cooling
coil
must
be
installed
parallel
with,
or on the
downstream
side of the unit to avoid
condensation
in the heat
exchangers.
When installed
parallel
with the furnace,
dampers
or
other
flow control
must
prevent
chilled
air from
entering
the
furnace.
If the
dampers
are manually
operated,
they
must
be
equipped
with
means
to prevent
operation
of either unit unless
the damper
is in the full-heat
or full-cool
position.
AIR
FOR
COMBUSTION
AND
VENTILATION
Provisions
for adequate
combustion,
ventilation,
and dilution
air
must be provided
in accordance
with:
Section
9.3 of the NFPA 54 / ANSI
Z223.1-2009,
Air
for Combustion
and Ventilation,
and applicable
provi-
sions of the local building
codes.
FURNACE
CORROSION
HAZARD
Failure to follow
this caution
may result in furnace
damage.
Air for combustion
nmst
not be contanfinated
by halogen
compounds,
which
include
fluoride,
chloride,
bronfide,
and
iodide.
These
elements
can corrode
heat exchangers
and
shorten
furnace
life. Air contanfinants
are found
in aerosol
sprays,
detergents,
bleaches,
cleaning
solvents,
salts,
air
fresheners,
and other household
products.
18-IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
Fig. 5 -
Installation
in a Garage

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pg8jaa

Table of Contents