Page 1
CLICK ANYWHERE on THIS PAGE to RETURN to PAYNE HVAC MANUALS & GUIDES at InspectApedia.com PG8M/PG8J Installation, Start-up, Operating, and Service and Maintenance Instructions -Series C The Payne PG8M/PG8J 80% AFUE Gas Furnaces feature 4- way multipoise design and through-the-furnace downflow venting.
Page 4
INSTALLATION MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES This forced air furnace is equipped for use with This furnace is approved for UPFLOW, DOWNFLOW, and HORIZONTAL installations. natural gas at altitudes 0-10,000 ft (0-3,050m). accessory kit, supplied...
→ Step 8—Venting • US: NFGC; chapters 10 and 13 • CANADA: NSCNGPIC Part 7 and Appendix C ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE → FURNACE RELIABILITY HAZARD Improper installation or service of furnace may cause prema- ture furnace component failure. Electrostatic discharge can affect electronic components.
Page 7
THE BLOWER IS LOCATED BELOW THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED UPWARD. THE BLOWER IS LOCATED TO THE RIGHT OF THE BURNER SECTION, AND AIR CONDITIONED AIR IS DISCHARGED TO THE LEFT. THE BLOWER IS THE BLOWER IS LOCATED TO THE LEFT LOCATED ABOVE THE BURNER SECTION, AND...
→ PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD Improper use or installation of this furnace may cause premature furnace component failure. This gas furnace may be used for heating buildings under construction provided that: -The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions.
Page 9
→ Table 2–Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS (1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ.
Page 10
1 SQ IN. PER 4000 CIRCULATING AIR DUCTS VENT THROUGH ROOF BTUH* DUCTS OUTDOORS 12″ MAX 12″ 12" MAX 1 SQ IN. VENT PER 2000 THROUGH BTUH* ROOF 1 SQ IN. 1 SQ IN. PER 1000 BTUH* IN DOOR 4000 OR WALL BTUH* UNCONFINED...
c. Combining space on different floor levels. The volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more perma- nent openings in doors or floors having free area of at least 2 in.
⁄ ″ Platform Furnace Support Construct working platform at location where all required furnace clearances are met. (See Fig. 2 and 17.) For furnaces with 1-in. ⁄ ″ clearance requirement on side, set furnace on non-combustible blocks, bricks or angle iron. For crawlspace installations, if the ⁄...
A02014 Fig. 16—Horizontal Suspension with Straps LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS, STUDS, OR FRAMING. ″ OVER ALL ″ UNDER DOOR 1″ UNDER FURNACE TYPE-B EXTEND OUT 12″...
Page 19
A02075 Fig. 18—Upflow Return Air Configurations and Restrictions A02163 Fig. 19—Downflow Return Air Configurations and Restrictions A02162 Fig. 20—Horizontal Return Air Configurations and Restrictions...
→ Table 6—Maximum Capacity of Pipe* ELECTRICAL SHOCK AND FIRE HAZARD NOMINAL LENGTH OF PIPE (FT) IRON INTERNAL Failure to follow this warning could result in serious injury, PIPE DIAMETER death, or property damage. SIZE (IN.) The cabinet MUST have an uninterrupted or unbroken ground (IN.) according to NEC ANSI/NFPA 70-2002 and Canadian Elec- 0.622...
Page 21
→ Table 7—Electrical Data OPERATING VOLTS- MAXIMUM MAXIMUM UNIT MAXIMUM MINIMUM VOLTAGE RANGE FURNACE SIZE HERTZ- FUSE OR CKT BKR UNIT AMPS AMPACITY# WIRE LENGTH (FT)‡ WIRE GAUGE PHASE AMPS† Maximum* Minimum* 045-08/024045 115-60-1 7.54 045-12/036045 115-60-1 9.50 070-08/024070 115-60-1 7.06 070-12/036070 115-60-1...
The following information and warning must be considered in addition to the requirements defined in the NFGC and the CARBON MONOXIDE POISONING HAZARD NSCNGPIC. Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
4. The input rating of each space heating appliance is greater Table B—Minimum Alowable Input Rating of than the minimum input rating given in Table B for the local Space-Heating Appliance in 99% Winter Design Temperature. Chimneys having internal Thousands of BTU per Hour areas greater than 38 square inches require furnace input ratings greater than the input ratings of these furnaces.
Page 26
CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211 Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian installation Code CSA-B149.1 in Canada. Crown Rebuild condition: crown.
4. Set the thermostat heat anticipator or cycle rate to reduce short cycling. → CUT HAZARD Air for combustion must not be contaminated by halogen com- Failure to follow this caution may result in personal injury. pounds which include chlorides, fluorides, bromides, and iodides. Sheet metal parts may have sharp edges or burrs.
A04131 → Fig. 31—Remove Knockout with Hammer START-UP, ADJUSTMENT, AND SAFETY CHECK Step 1—General A04128 → Fig. 28—Rounded End of Knockout FIRE HAZARD Failure to follow this warning could result in a fire and lead to property damage, personal injury, or death. This furnace is equipped with manual reset limit switches in the gas control area.
Page 29
SEE NOTES: 1,2,4,5,7,8,9 SEE NOTES: 1,2,4,7,8,9 on the page following on the page following these figures these figures A03208 A03211 Fig. 32—Upflow Application-Vent Elbow Up Fig. 35—Downflow Application-Vent Elbow Up SEE NOTES: 1,2,4,5,6,7,8,9,10 SEE NOTES: 1,2,3,4,7,8,9 on the page following these figures on the pages following Fig.
Page 30
SEE NOTES: 1,2,4,7,8,9 on the page following these figures SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures A03213 Fig. 38—Horizontal Left Application-Vent Elbow Left A03215 Fig. 40—Horizontal Left Application-Vent Elbow Up SEE NOTES: 1,2,4,5,7,8,9 on the page SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures A03214 A03216...
Page 31
SEE NOTES: 1,2,4,5,7,8,9 A02068 Fig. 44—Horizontal Right Application-Vent Elbow Left Venting Notes for Figures 32-44 1. For common vent, vent connector sizing and vent material: United States--use the NFGC Canada--use the NSCNGPIC 2. Immediately increase to 5-inch or 6-inch vent connector outside furnace casing when 5-inch vent connector is required, refer to Note 1 above. 3.
1. Determine the correct gas input rate. In the U.S.A.: ELECTRICAL SHOCK HAZARD The input rating for altitudes above 2,000 ft. must be reduced Failure to follow this warning could result in electrical shock, by 4 percent for each 1,000 ft. above sea level. For installa- personal injury, or death.
THERMOSTAT SUBBASE Table 9—Speed Selection TERMINALS WITH THERMOSTAT REMOVED COLOR SPEED AS SHIPPED (ANITICIPATOR, CLOCK, ETC., White Common MUST BE OUT OF CIRCUIT.) Black High COOL HOOK-AROUND Yellow† Med-High SPARE AMMETER Blue* Med-Low SPARE Red* HEAT * 1/5 HP motor models: BLUE to HEAT, RED to SPARE. R Y W G †...
status code 32. If hot surface igniter glows when inducer Table 10–GAS RATE (CU FT/HR) motor is disconnected, shut down furnace immediately. SIZE OF TEST DIAL SIZE OF TEST DIAL SECONDS SECONDS e. Determine reason pressure switch did not function properly FOR 1 FOR 1 and correct condition.
SERVICE If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After status code recall is completed component test will occur. LED CODE STATUS CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
4. Inspect burner compartment before each heating season for Table 11—FILTER SIZE INFORMATION (IN.) rust, corrosion, soot or excessive dust. If necessary, have FILTER QUANTITY AND SIZE furnace and burner serviced by a qualified service agency. FURNACE FILTER CASING WIDTH TYPE Side Return Bottom Return...
Page 39
TABLE 12—Orifice Size* and Manifold Pressure For Gas Input Rate (Tabulated Data Based On 22,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level) SPECIFIC GRAVITY OF NATURAL GAS ALTITUDE AVG GAS 0.58 0.60 0.62 0.64 RANGE HEAT VALUE Orifice...
Page 40
Table 12—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued) (Tabulated Data Based On 22,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level) SPECIFIC GRAVITY OF NATURAL GAS AVG GAS ALTITUDE HEAT VALUE 0.58 0.60 0.62 0.64...
Table 12—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued) (Tabulated Data Based On 22,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level) SPECIFIC GRAVITY OF NATURAL GAS AVG GAS ALTITUDE HEAT VALUE 0.58 0.60 0.62 0.64...
Page 42
TABLE 13—Orifice Size* and Manifold Pressure For Gas Input Rate (Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level) SPECIFIC GRAVITY OF NATURAL GAS ALTITUDE AVG GAS 0.58 0.60 0.62 0.64 RANGE HEAT VALUE Orifice...
Page 43
Table 13—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued) (Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level) SPECIFIC GRAVITY OF NATURAL GAS AVG GAS ALTITUDE HEAT VALUE 0.58 0.60 0.62 0.64...
Page 44
Table 13—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued) (Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level) SPECIFIC GRAVITY OF NATURAL GAS AVG GAS ALTITUDE HEAT VALUE 0.58 0.60 0.62 0.64...
b. Igniter Warm-Up- At the end of the prepurge period, the Hot-Surface Igniter HSI is energized for a 17-second igniter warm-up period. → c. Trial-for-Ignition Sequence- When the igniter warm-up period is completed the main gas valve relay contacts GVR close to energize the gas valve GV, the gas valve opens.
period at HEAT speed. the blower switches to COOL speed after a 3 second delay. If When the thermostat ″calls for cooling″, the blower motor the R-to-W-and-Y-and-G signals disappear at the same time, BLWM will operate at COOL speed. When the thermostat is the blower motor BLWM will remain on for the selected satisfied, the blower motor BLWM will operate an additional blower-OFF delay period.
Page 49
Copyright 2005 Carrier Corporation 58st13si Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. See Cover Printed in U.S.A. Form 58ST-13SI Pg 48 5-05 Replaces: 58ST-12SI Tab 6a 8a...
Need help?
Do you have a question about the C Series and is the answer not in the manual?
Questions and answers