Step 1: Ventilation - Thermador PRO-HARMONY PRG30 Installation Manual

Professional pro-harmony gas ranges
Hide thumbs Also See for PRO-HARMONY PRG30:
Table of Contents

Advertisement

Available languages

Available languages

appliance should beinstalled in accordance withthe
National FuelGasCode ANSIZ223.1/NFPA 54current
issueandNational Electrical CodeANSI/NFPA 7 0-current
issue. I nCanada, i nstallation m ustbeinaccordance with
theCAN1-B149.1 a nd.2- Installation C odes forGas
Burning Appliances a nd/or l ocal c odes.
It istheresponsibility oftheowner andtheinstaller to
determine ifadditional requirements and/or s tandards
apply to specific installations.
Step 1: Ventilation
Requirements
It is stronqly recommended that a suitable exhaust hood be
installed above the range. Downdraft ventilation should not
be used. The following table indicates the ventilation hood
options and blower capacity guidelines that are
recommended for use with all Thermador ranges.
,
Select Hood and Blower Models:
For wall installations, the hood width must, at a
minimum, equal the width of the range cooking surface.
Where space permits, a hood larger in width than the
3.
cooking surface may be desirable for improved
ventilation performance.
For island installations, the hood width should, at a
minimum, overhang the range cooking surface by 3" on
each side.
Important:
Ventilation hoods and blowers are designed for use with
single wall ducting. However, some local building codes or
inspectors may require double wall ducting. Consult local
building codes and/or local agencies, before starting, to
assure that hood and duct installation will meet local
requirements.
Do not install a microwave oven/ventilator
combination
above the range, as these type of units do not provide the
proper ventilation and are not suitable for use with the
range.
2.
Hood Placement:
For best smoke elimination, the lower edge of the hood
should be installed 30" above the range cooking
surface. (See Figure 1).
NOTICE:
Most range hoods contain combustible components which
must be considered when planning the installation.
If the hood contains any combustible materials (i.e. a
wood covering), it must be installed a minimum of 40"
above the cooking surface.
Consider Make-Up Air:
Due to the high volume of ventilation air, a source of
outside replacement air is recommended. This is
particularly important for tightly sealed and insulated
homes.
A qualified heating and ventilating contractor should be
consulted.
_____________
_ ______________
30" or 36" Pro Wall Hood
30"
4 burners
800 CFM
30" or 36" Custom Insert w/optional
blower
42" Island Hood w/optional
blower
4 burners with griddle
1,000 CFM
36" or 42" Pro Wall Hood
36"
36" Custom Insert w/optional
blower
6 burners
1,100 CFM
42" or 48" Island Hood w/optional
blower
English 3