Typical Heat/Cool Speed Tap Connections; Filter Performance - Pressure Drop Inches W.c. And (Kpa) - Coleman UGAE Installation Manual

High efficiency clam tube heat exchanger series
Hide thumbs Also See for UGAE:
Table of Contents

Advertisement

98618/035-20009-001
Rev. B (1205)
The temperature
rise, or temperature difference between the return air
and the heated supply air from the furnace,
must be within the range
shown on the furnace rating plate and within the application
limitations
as shown in Table 8.
After about 20 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts,
about six feet (1.83 m) from the furnace where they will not be affected
by radiant heat. Increase the blower speed to decrease the temperature
rise; decrease the blower speed to increase the rise.
All direct-drive
blowers have multi-speed
motors.
The blower
motor
speed taps are located in the control box in the blower compartment.
Refer to Figure 24, and the unit wiring label to change the blower
speed. To use the same speed tap for heating and cooling, the heat ter-
minal and cool terminal must be connected
using a jumper wire and
connected to the desired motor lead. Place all unused motor leads on
Park terminals. Two are provided.
CAUTION1
Do not energize more than one motor speed at a time or damage to
the motor will result,
ADJUSTMENT
OF FAN
CONTROL
SETTINGS
This furnace is equipped with a time-on/time-off
heating fan control. The
fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,
90, 120 and 180 seconds). The fan off delay is factory set to 120 sec-
onds. The fan-off setting must be long enough to adequately
cool the
furnace, but not so long that cold air is blown into the heated space. The
fan-off timing may be adjusted
by positioning the jumper on two of the
four pins as shown in Figure 25.
TABLE 12: Filter Performance - Pressure Drop Inches W.C. and (kPa)
60
180
FIGURE 24: Typical Heat/Cool Speed Tap Connections
FILTER
PERFORMANCE
The airflow capacity data published in Table 13 represents
blower per-
formance WITHOUT filters. To determine the approximate
blower per-
formance of the system, apply the filter drop value for the filter being
used or select an appropriate
value from the Table 12.
The filter pressure drop values in Table 12 are typical values for the
type of filter listed and should only be used as a guideline. Actual pres-
sure drop ratings for each filter type vary between filter manufacturers.
Airflow Range
Minimum Opening Size
Disposable
Filter Type
Hogs Hair*
Pleated
2 Openings
1 Opening
2 Openings
1 Opening
2 Openings
inwc I kPa
inwc
kPa
inwcl
kPa
inwc
kPa
inwcl
kPa
i
i
i
0.05
0.0125
0.2
0.0498
0.1
0.0249
0.2
0.0498
0.1
0.0249
0.25
0.0623
0"11101027410118 0"0448 0"1 10102491
0 .3
0.074710.1710.042
Example: For a 75,000 BTUH (21.98 kW) furnace with 2 return open-
ings and operating on high-speed
blower, it is found that total system
static is 0.38" w.c. To determine the system airflow, complete the follow-
ing steps:
Obtain the airflow values at 0.30 w.c. (75 Pa) & 0.40 w.c. (99.6Pa) ESR
Airflow @ 0.30": 1408 CFM (39.8 m3/min)
Airflow @ 0.40": 1343 CFM (38.0 m3/min)
Subtract the airflow @ 0.30 w.c. (75 Pa) from the airflow @ 0.40 w.c.
(99.6 Pa) to obtain airflow difference.
1343 - 1408 = -65 CFM (1.89 m3/min)
Subtract the total system static from 0.30 w.c. (75 Pa) and divide this
difference
by the difference
in ESP values
in the table, 0.40 w.c.
(99.6 Pa) - 0.30 w.c. (75Pa), to obtain a percentage.
(0.38- 0.30) ! (0.40- 0.30) = 0.8
Multiply percentage
by airflow difference to obtain airflow reduction.
(0.8) X (-65) = -52
Subtract airflow reduction value to airflow @ 0.30 w.c. (75 Pa) to obtain
actual airflow @ 0.38 inwc (94.6 Pa) ESR
1408 - 52 = 1356
1 Opening
2 Openings
1 Opening
CFM
Cm/m
In 3
m3
In_
m _
inwc
kPa
o7 o oooo 8; l ! OOlO
751 - 1000
21.27-
28.32
330
0.0054
0.05
0.0125
1001 - 1250
28.35-
35.40
330
0.0054
0.1
0.0249
1251 - 1500
35.42 - 42.47
330
0.0054
0.1
0.0249
1501 - 1750
42.50-49.55
380
010062 ..................................
.............................................................
0.15
010374
1751-2000
49158-56.63
380
0100621 658 1010108 0119 010473 I
Hogs Hair Filters are the type supplied with furnace (if supplied).
APPLYING
FILTER
PRESSURE
DROP
TO
DETERMINE
SYSTEM
AIRFLOW
To determine the approximate
airflow of the unit with a filter in place, fol-
low the steps below:
1.
Select the filter type.
2.
Select the number of return air openings
or calculate
the return
opening size in square inches to determine the proper filter pres-
sure drop.
3.
Determine the External System Static Pressure (ESP) without the
filter.
4.
Select a filter pressure drop from the table based upon the number
of return air openings
or return air opening size and add to the
ESP from Step 3 to determine the total system static.
5.
If total system static matches a ESP value in the airflow table (i.e.
0.20 w.c. (50 Pa), 0.60 w.c. (150 Pa), etc.,) the system airflow cor-
responds to the intersection of the ESP column and Model/Blower
Speed row.
6.
If the total system static falls between ESP values in the table (i.e.
0.58 w.c. (144 Pa), 0.75 w.c. (187 Pa), etc.), the static pressure
may be rounded to the nearest value in the table determining
the
airflow using Step 5 or calculate the airflow by using the following
example.
20
Unitary Products Group

Advertisement

Table of Contents
loading

Table of Contents