Coleman UGAE Installation Manual

High efficiency clam tube heat exchanger series
Hide thumbs Also See for UGAE:

Advertisement

Quick Links

.........................................
14
', H',
,'1.-¢" 'l.I
HIGH EFFICIENCY
CLAM TUBE HEAT EXCHANGER
SERIES
MODEL:
UGAE
(Single
Stage
Upflow
Only)
75 MBH INPUT
(21.98
KW)INPUT
ISO 9001
Certified Quality
Management
System
!
I
TABLE OF CONTENTS
SAFETY
................................................
1
TWINNING AND STAGING
................................
11
DUCTWORK
............................................
4
VENT/COMBUSTION
AIR SYSTEM
.........................
12
FILTERS
...............................................
6
SAFETY CONTROLS
....................................
16
GAS PIPING
............................................
7
START-UP AND ADJUSTMENTS
...........................
17
ELECTRICAL
POWER
...................................
10
WIRING DIAGRAM
......................................
22
LIST OF FIGURES
Dimensions
.............................................
5
Floor Installation
..........................................
6
Platform Installation
.......................................
6
Side Return Cutout Markings
................................
6
External Air Filter Rack - Left & Right Side Position
..............
7
External Air Filter Rack - Bottom Position
......................
7
Gas Valve ...............................................
7
Gas Piping Configuration
...................................
8
Burner Assembly
.........................................
8
Line Wiring Connections
..................................
10
Heating and Cooling Thermostat
Connections
.................
10
Accessory Connections
...................................
11
Typical Twinned Furnace Application
........................
11
Single Stage Twinning Wiring Diagram
.......................
12
Two-Stage Twinning Wiring Diagram
.........................
12
Roof Jack
..............................................
13
Roof Jack Assembly
......................................
14
Roof Jack Installation
.....................................
14
Ceiling Ring
............................................
14
Home Layout
...........................................
15
Pressure Switch Tubing Routing
............................
16
Gas Valve
..............................................
19
Reading Gas Pressure
....................................
19
Typical Heat/Cool Speed Tap Connections
....................
20
Wiring Diagram
..........................................
22
LIST OF TABLES
Unit Clearances
to Combustibles
.............................
4
Minimum Duct Sizing For Proper Airflow
.......................
5
External Static Pressure Range ..............................
5
Cabinet and Duct Dimensions
...............................
5
Filter Sizes - Upflow .......................................
7
Inlet Gas Pressure Range
..................................
8
High Altitude Conversion
...................................
9
Ratings & Physical/Electrical
Data - Upflow Models .............
10
Roof Jack Options
.......................................
14
Inlet Gas Pressure Range
.................................
19
Nominal Manifold Pressure .................................
19
Filter Performance
- Pressure Drop Inches W.C. and (kPa) ........
20
Blower Performance
CFM
.................................
21
Field Installed Accessories
- Non Electrical
....................
21
Field Installed Accessories
- Electrical
........................
21
SECTION
h SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals,
be alert to the potential
for personal
injury.
Understand
and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER
indicates an imminently
hazardous
situation, which, if not
avoided, will result in death or serious injury.
WARNING
indicates a potentially
hazardous
situation, which, if not
avoided, could result in death or serious iniurv.
CAUTION
indicates a potentially
hazardous
situation,
which, if not
avoided mav result in minor or moderate
iniurv. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
AWARNING
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper
installation,
adjustment,
alteration,
service
or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information,
consult a qualified con-
tractor, installer or service agency.
CAUTION
This product must be installed in strict compliance
with the installa-
tion instructions
and any applicable local, state, and national codes
including,
but not limited to building,
electrical,
and mechanical
codes.
98618/035-20009-001
Rev. B (1205)

Advertisement

Table of Contents
loading

Summary of Contents for Coleman UGAE

  • Page 1 ......... ', H', ,'1.-¢" 'l.I HIGH EFFICIENCY CLAM TUBE HEAT EXCHANGER SERIES MODEL: UGAE ISO 9001 (Single Stage Upflow Only) Certified Quality Management System 75 MBH INPUT (21.98 KW)INPUT TABLE OF CONTENTS SAFETY ..........TWINNING AND STAGING ........ DUCTWORK ..........
  • Page 2 98618/035-20009-001 Rev. B (1205) SPECIFIC SAFETY RULES PRECAUTIONS Filter must be installed in the furnace as specified in the installation instructions, and must be replaced or thoroughly Only Natural gas or Propane (LP) gas are approved for use with cleaned prior to occupancy of the home. Again, drywall dust this furnace.
  • Page 3 98618/035-20009-001 Rev. B (1205) Provide clearances from combustible materials as listed under AWARNING Furnace Locations and Clearances. Provide clearances for servicing ensuring that service access is allowed for both the burners and blower. The furnace area must not be used as a broom closet or for any These models are CSA listed and approved for installation into a other storage purposes, as a fire hazard may be created.
  • Page 4: Installation

    98618/035-20009-001 Rev. B (1205) Clearances for access: In all cases, accessibility clearances shall take precedence over clear- Ample clearances should be provided to permit easy access to the unit. ances for combustible materials where accessibility clearances The following minimum clearances are recommended: greater.
  • Page 5: Dimensions

    98618/035-20009-001 Rev. B (1205) Consideration should be given to the heating capacity required and also ommended rectangular duct height is 4 inches (10 cm) attached to the plenum. to the air quantity (CFM) required. These factors can be determined calculating the heat loss and heat gain of the home or structure. If these IMPORTANT: The air temperature rise should be taken only after the...
  • Page 6: Filters

    98618/035-20009-001 Rev. B (1205) PLATFORM INSTALLATIONS MANUFATURED (MOBILE) HOME MODULAR HOME UPFLOW RETURN PLENUM CONNECTION As shown in Figure 3, the furnace may be installed on a raised platform. Return air may enter the furnace through the side(s) or bottom depend- The platform must be a minimum of 20"...
  • Page 7: Gas Piping

    98618/035-20009-001 Rev. B (1205) EXTERNAL INSTALLATION UPFLOW CONFIGURATIONS [][][][][][][][] Select desired filter position for upflow (left/right side, side and bot- tom). Remove the corresponding cabinet cutouts per instructions r---q provided. Install the external filter box to the side of the cabinet and secure to the cabinet as specified in the instructions provided with the air filter FURNACE kit.
  • Page 8: Gas Piping Configuration

    98618/035-20009-001 Rev. B (1205) CHECKING THE GAS PRESSURES CAUTION The pressure ports on the gas valve are marked OUT P and IN The gas valve body is a very thin casting that cannot take any The manifold pressure must be taken at the port marked OUT R external pressure.
  • Page 9: High Altitude Conversion

    98618/035-20009-001 Rev. B (1205) CONVERSION PROCEDURE HIGH ALTITUDE ORIFICE CONVERSION This furnace is constructed at the factory for natural gas-fired operation CAUTION at 0 - 2,000 ft. (0 m - 610 m) above sea level. The gas orifices on this furnace must be changed in order to maintain The gas supply must be shut off prior to disconnecting the electrical proper and safe operation, when the furnace is installed in a location...
  • Page 10: Electrical Power

    98618/035-20009-001 Rev. B (1205) SECTION V: ELECTRICAL POWER [& CAUTION Electrical Power Connections Field wiring to the unit must be grounded. Electric wires that are field Use copper conductors only. installed shall conform to the temperature limitation for 63°F (35°C) rise wire when installed in accordance with instructions.
  • Page 11: Accessory Connections

    98618/035-20009-001 Rev. B (1205) VENT PIPE ELECTRICAL GAS SUPPLY SUPPLY SIDES) 1 COIL FOR VO LT-------_ ELECTRONIC IWHT CLEANER [----q FIGURE 12: Accessory Connections ELECTRONIC CLEANER CONNECTION FIGURE 13: Typical Twinned Furnace Application Two 1!4" (0.6 cm) spade terminals (EAC and EAC N) for electronic air IMPORTANT: When two furnaces are twinned, typical system total air- cleaner connections...
  • Page 12: Single Stage Twinning Wiring Diagram

    98618/035-20009-001 Rev. B (1205) Single-Wire Twinning Instructions Single-Wire Staging Connect the control wiring as shown in the Figure 14. The single-wire twinning feature of this board can also be used for stag- ing of two furnaces. With this feature, a single wire is connected Connect the low voltage wiring from the wall thermostat to the ter- between the TWIN terminal on one furnace board to the TWIN terminal minal strip on the control board of Furnace #1.
  • Page 13: Roof Jack

    98618/035-20009-001 Rev. B (1205) CATEGORY 1 - 450 R MAX. VENT TEMR The venting system must be IMPORTANT: The "VENT SYSTEM" must be installed as specified installed in accordance with Section 5.3,Air for Combustion and Ventila- these instructions Manufactured (Mobile) Home and Modular Homes.
  • Page 14: Roof Jack Assembly

    98618/035-20009-001 Rev. B (1205) ROOF JACK MUST _r ......¢,, ...._ FLUE BE 4000 SERIES " AS SHOWN GASES COM_INT CAULK UNDER "COMBUSTION AIR AIR PIPE AND MUST BE FLASHINGS _ CAULK SWIVEL FLUE ASSEMBLY _BELOW CEILING WARM AIR _-] m J°...
  • Page 15: Home Layout

    98618/035-20009-001 Rev. B (1205) .... i ,-- VENT TERMINAL AIR SUPPLY AREA WHERE TERMINAL IS NOT PERMITTED "\. FIXED CLOSED \"_ OPERABLE FIGURE 20: Home Layout Canadian Installations I US Installation 2 A. Clearance above grade, veranda, porch, deck, or balcony 12 inches (30 cm) 12 inches (30 cm) 6 inches (15 cm) for applications...
  • Page 16: Safety Controls

    98618/035-20009-001 Rev. B (1205) _WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation: 1.
  • Page 17 98618/035-20009-001 Rev. B (1205) SECTION IX: START-UP IGNITION SYSTEM SEQUENCE ADJUSTMENTS Turn the gas supply ON at external valve and main gas valve. The initial start-up of the furnace requires the following additional Set the thermostat above room temperature to call for heat. procedures: System start-up will occur as follows: IMPORTANT: All electrical connections...
  • Page 18 98618/035-20009-001 Rev. B (1205) In the USA use the following formula to calculate the furnace input. For natural gas multiply the heat content of the gas BTU/SCF (or Default 1030 BTU/SCF, times 2 cubic ft. of gas measured at the gas meter, times a barometric pressure and temperature correction factor of 0.960;...
  • Page 19: Gas Valve

    98618/035-20009-001 Rev. B (1205) IMPORTANT: If gas valve regulator is turned in (clockwise), manifold CAUTION pressure is increased. If screw is turned out (counterclockwise), mani- fold pressure will decrease. After the manifold pressure has been adjusted, re-calculate Be sure to relight any gas appliances that were turned off at the furnace input to make sure you have not exceeded the specified...
  • Page 20: Typical Heat/Cool Speed Tap Connections

    98618/035-20009-001 Rev. B (1205) The temperature rise, or temperature difference between the return air and the heated supply air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations as shown in Table 8. After about 20 minutes of operation, determine the furnace temperature rise.
  • Page 21 98618/035-20009-001 Rev. B (1205) TABLE 1 3: B lower Performance UPFLOW, SINGLE SIDE RETURN (WITHOUT FILTER) EXTERNAL STATIC PRESSURE, INCHES WC (kPa) BTU/H (kW) Cabinet Speed 0.1 (0.025) 0.2 (0.050) 0.3 (0.075) 0.4 (0.099) 0.5 (0.124) 0.6 (0.149) 0.7 (0.174) 0.8 (0.199) Input / Output Size...
  • Page 22 0") CONNECTION DIAGRAM BLO_YER SPEED CHART 1fIRE COLOR (DIAGRAM._IE DE RACCORDEMENT) (CODE DE COILEUR (CttARTE DE VlTESSE DE LA SOUFPLERIE) FILAGE Ix.) BLK ii ( NOI IA r ) %E E_A_ (MOrEuR SOdFr:LERIE) .." {3ESI E? (/<}i BWER SPEEI {][J r_i i :_fT>'...
  • Page 23 98618/035-20009-001 IRev. B (1205) NOTES Unitary Products Group...
  • Page 24 NOTES 98618/035-20009-001 Rev. B (1205) Subject to change without notice. Printed in U.S.A. Supersedes: 035-20009-001 Rev. A (0704) Copyright _> by York International Corp. 2005. All rights reserved. 5005 Norman Unitary Product York Drive 73069 Group...

Table of Contents