Wiring For Heat Only Thermostat; Ratings & Physical / Electrical Data; Wiring For Electronic Heat-Cool Thermostat; Wiring For Standard Heat-Cool Thermostat - Coleman DGAA Installation Manual

High efficiency sealed combustion gas furnace (single stage downflow only) 56-90 mbh input (16.41 -26.38 kw)input
Table of Contents

Advertisement

129098-UIM-H-1011
Eighteen gauge thermostat
wire is highly recommended,
Smaller gauge thermostat wire may be used only if the guideline below
is followed.
Thermostat
Wire Length
Thermostat
Wire Gauge
(Furnace to Thermostat)
0 - 45 feet
22
0 - 70 feet
20
Do not use the thermostat
wire smaller than 22 gauge.
If thermostat
wire small than 18 gauge is used, pay particular attention that the con-
nections between the different wire sizes are tight.
Operational
problems may be caused by loose connections
or by the
use of thermostat wire that is too small to carry the required load. Any
such problems are the responsibility
of the installer.
A separate
115 V.A.C. supply circuit must be used for the furnace. The
circuit should be protected by a 15 amp fuse or circuit breaker.
Avoid locations
where the thermostat
could be subject to drafts from
outside, or exposed to direct light from lamps, sun, fireplaces,
etc., or
affected by air from a duct register blowing directly on the thermostat.
The wall thermostat
should be located 52 to 66 inches above the floor.
The preferred location is on an inside wall situated in an area with good
air circulation,
and where the temperature
will be reasonably
represen-
tative of other living areas the thermostat is controlling.
ROOM
FURNACE
THERMOSTAT
CONTROL
il
FIGURE 17: Wiring for Heat Only Thermostat
ROOM
FURNACE
CONDENSING
THERMOSTAT
CONTROL
UNIT
....
.........
FIGURE 18: Wiring for Electronic Heat-Cool Thermostat
ROOM
FURNACE
CONDENSING
THERMOSTAT
PIGTAILS
UNIT
FIGURE 19: Wiring for Standard Heat-Cool Thermostat
UN,TCONDENS'NG
TO AIR
CONDITIONER
CONTROLS
[ BLENDAIR
I
CONTROL
BOX
FIGURE 20: Wiring for Blend Air Accessory
TABLE 5: Ratings & Physical / Electrical Data
Input
MBH
I
kW
DGAA SERIES
56
16
70
21
77
23
90
26
DGAH SERIES
56
16
77
23
Output
MBH I
kW
Nominal 1
CFM(m3/min)
CFM I cmm
Cabinet Width
In.
I
cm
Air Temp, Rise
AFUE
°F
I
°C
Operation
Wgt.
LBS
I
Kg
45
13
1305
37
19-1/2
49.5
80.0
45 - 75
25 - 41.7
163
73.9
56
16
1305
37
19-1/2
49.5
80.0
45 - 75
25 - 41.7
163
73.9
62
18
1305
37
19-1/2
49.5
80.0
45 - 75
25 - 41.7
163
73.9
72
21
1305
37
19-1/2
49.5
80.0
45 - 75
25 - 41.7
163
73.9
45
13
1050
30
19-1/2
49.5
80.0
45 - 75
25 - 41.7
146
66.2
62
18
1050
30
19-1/2
49.5
80.0
45 - 75
25 - 41.7
146
66.2
Max. Outlet
Booster Motor
Max
Min, wire Size
Input
Air Temp
Blower
Blower Size
Total Unit
Ignitor
& Gas Valve
Over-Current
(awg) @ 75 ft
MBH I kW
°F I °C
Hp
lAmps In. I
cm
Amps
Amps
Amps
Protect
one
way
DGAA SERIES
56
16
165
73.9
1/3
7.3
10x8
25.4 x 20.3
12.0
4.1
0.6
15
14
70
21
165
73.9
1/3
7.3
10 x 8
25.4 x 20.3
12.0
4.1
0.6
15
14
77
23
165
73.9
1/3
7.3
10 x 8
25.4 x 20.3
12.0
4.1
0.6
15
14
90
26
165
73.9
1/3
7.3
10 x 8
25.4 x 20.3
12.0
4.1
0.6
15
14
DGAH SERIES
56
16
165
73.9
1/6
7.8
10x8
25.4 x 20.3
12.4
4.1
0.6
15
14
77
23
165
73.9
1/6
7.8
10 x 8
25.4 x 20.3
12.4
4.1
0.6
15
14
Slower - High Speed
1. 0.3" Ext. Static Duct Pressure - No Coil - Std.
SECTION
VII:
ROOF
JACK
VENT/
COMBUSTION
AIR
SYSTEM
VENT
AND
COMBUSTION
AIR
SAFETY
The venting system must be installed in accordance with Section 5.3,Air
for Combustion
and Ventilation,
of the National Fuel Gas CodeZ223.1/
NFPA 54 (latest edition),
or Sections
7.2, 7.3 or 7.4 of CAN/CGA
B149.1-00, National Gas and Propane Codes (latest edition) or applica-
ble provisions of the local building code and these instructions.
The fur-
nace shall not be connected
to any chimney, a flue serving a separate
appliance, or any appliance designed to burn solid fuel. The furnace rat-
ing plate lists the maximum vent gas temperature.
This Category
I, furnace is designed for Manufactured
(Mobile) Home
and Modular Home application.
It may be installed without modification
in a garage, equipment room, alcove or any other indoor location where
all required clearance
to combustibles
and other restrictions are met,
AND providing factory Roof Jack System meets all installation require-
ments.
Johnson Controls Unitary Products
13