Sequence Of Operation; Troubleshooting; Safety Section; Burner Removal/Cleaning - Coleman 268897-UUM-B User Manual

Single-stage upflow, 92% afue, manufactured housing or modular home applications
Table of Contents

Advertisement

268897-UUM-B-1108
SECTION
Ih SERVICE
AND
MAINTENANCE
MANUAL
SAFETY
SECTION
The following
safety rules must be followed
when servicing
the
furnace.
,WARNING
ELECTRIC
SHOCK, FIRE OR EXPLOSION
HAZARD
Failure
to follow safety
warnings
exactly could
result in
dangerous
operation,
serious
injury,
death or property
damage.
Improper
servicing
could
result in dangerous
operation,
serious
injury, and death or property
damage.
Before servicing,
disconnect
all electrical
power to the fur-
Race.
When servicing controls, label all wires prior to disconnect-
ing. Reconnect wires correctly.
Verify proper operation after servicing.
FURNACE
MAINTENANCE
SECTION
The furnace should be cleaned
and adjusted
by a certified dealer or
qualified service contractor
once a year or before the start of every
heating season. The following
items must be cleaned and serviced or
replaced if there are signs of deterioration.
1.
The vent terminal.
2.
The furnace vent and combustion air intake passageways.
Should
it be necessary to service the vent/air intake system, the manufac-
turer recommends
this service be conducted by a qualified service
agency. The operation
of this appliance
requires the reassembly
and resealing of the vent/air intake system.
3.
The furnace burners, ignitor and flame sensor.
4.
The condensate
collection and disposal system. If any disassem-
bly of components
containing
flue or vent gases is required,
a
qualified service agency must perform the service.
FURNACE
CLEANING
SECTION
NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.
Burner
Removal/Cleaning
The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:
1.
Turn off the electrical
power to the unit.
2.
Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3.
Remove the burner door and remove the burner box cover.
4.
Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
5.
Remove the screws that hold the burner box assembly
to the vest
panel and remove the assembly.
6.
Remove burners from the burner assembly.
7.
Burners may be cleaned by rinsing in hot water.
8.
Reassemble the burners in the reverse order.
Cleaning
the Heat Exchanger
1.
Turn off the electrical
power to the unit.
2.
Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3.
Remove the burner door and remove the burner box cover.
4.
Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
5.
Remove the screws that hold the burner box assembly
to the vest
panel and remove the assembly.
6.
Remove the vent pipe assembly, vent blower and condensate
pan.
7.
The heat exchanger is now exposed.
8.
With a long flexible wire brush, clean inside each tube at both the
top and bottom.
The brush must
pass around
the rear heat
exchanger tubes. Then vacuum loose the scale and dirt from each
tube.
9.
Replace all components in reverse order. Reconnect all wiring.
10.
Restore electrical power and gas supply to the furnace.
11.
Check furnace operation.
CAUTION
Label all wires prior
to disconnection
when servicing
controls.
Wiring errors
can cause improper
and danger-
ous operation. Verify proper
operation after servicing.
Cleaning
the Secondary
Heat Exchanger
1.
Follow steps 1 - 7 under cleaning the Heat Exchanger.
2.
Remove the vent piping from the vent blower housing. Disconnect
the drain lines from the vent blower housing and from the conden-
sate drain pan. Remove the vent blower housing blower and the
condensate pan.
3.
Using a stiff wire brush, remove the loose scale or soot from each
tube.
4.
Vacuum the secondary heat exchanger.
5.
Finish the cleaning
procedure
by following
steps 9 - 11 under
cleaning the Heat Exchanger.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1.
Check to see that the power to the furnace and the ignition control
module is ON.
2.
The manual shut-off valves in the gas line to the furnace must be
open.
3.
Make sure all wiring connections are secure.
4.
Review the sequence of operation. Start the system by setting the
thermostat
above the room temperature.
Observe
the system's
response. Then use the troubleshooting
section in this manual to
check the system's operation.
AWARNING
Never bypass
pressure
switch
to allow
furnace
opera-
tion. To do so will allow furnace
to operate
under poten-
tially hazardous
conditions.
Do not try to repair controls.
Replace defective
controls
with UPG Source
1 Parts.
Never adjust pressure
switch
to allow furnace
operation.
SEQUENCE
OF OPERATION
The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.
Continuous
Blower
Cooling/heating
thermostats
have a fan switch that has an ON and
AUTO position. In the ON position the thermostat
circuit is completed
between terminals
R and G. The motor will operate on the speed tap
wire that is connected to the "HI COOL" cooling terminal on the control
board. To obtain a constant air circulation at lower flow rate, change the
high-speed wire to either the medium speed wire or the low speed wire.
Johnson Controls Unitary Products
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

UgadUgaeUgaf

Table of Contents