Troubleshooting Charts - Dunkirk 90-50 Installation, Operation & Maintenance Manual

Gas-fired, directvent, condensing, hot water boiler
Table of Contents

Advertisement

TROUBLESHOOTING CHART S
CHART 4
CHART 4
YES
I
YES
POSSIBLY
MIXTURE
TOO LEAN!
CHECK
GAS LINES
DOWNSTREAM
OF GAS
VALVE
FOR BLOCKAGE.
ARE
GAS LINES
CLEAR?
IS GAS/VENTURI
VALVE
CORRECT
SIZE?
SEE REPAIR
PARTS
DIAGRAM.
POSSIBLY
MITURE
TOO RICH!
CHECK
FLUE
PASSAGES
IN BOILER
PER
"MAINTENANCE
AND
CLEANING".
ARE
FLUE
PASSAGES
IN BOILER
CLEAN?
,_YES
CHECK
MIXER
AND
BURNER
FOR
BLOCKAGE
PER MAINTENANCE
AND
CLEANING
INSTRUCTIONS.
ARE AIR
PASSAGES
IN MIXER
AND
BURNER
CLEAN?
4,
CHECK
AIR ORIFICE
AT BURNER
INLET
FOR CORRECT
SIZE. SEE REPAIR
PARTS
DIAGRAM.
IS ORIFICE
CORRECT
SIZE?
CLEAN/REPLACE GAS LINES.
BE SURE TO USE CORRECT GASNENTURI VALVE SIZE.
CLEAN
BOILER
FLUE
PASSAGES
PER MAINTENANCE
AND CLEANING
INSTRUCTIONS
CLEAN
MIXER
AND BURNER
PER MAINTENANCE
AND
CLEANING
INSTRUCTIONS
REPLACE
BURNER
_r
DOES
MAIN
BURNER
RUN UNTILCALLFOR
HEAT ENDS
OR HI
LIMIT AQUASTAT
CONTACTS
OPEN?
NO#1
NO #2
NO #3
q
* IF THE ANSWER
IS NO.
CHOOSE
THE APPROPRIATE
PATH (#1, #2, OR #3) BASED
ON
_r
CHART
6
SYMPTOMS
SHOWN.
CHART
6
CHART
6
i
RUNS
SMOOTHLY
FOR ABOUT
6
SECONDS
THEN
SHUTS
OFF.
INDICATES
POOR
FLAME
SIGNAL.
CHECK
IGNITER/SENSOR
POSITION.
TIP SHOULD
BE
SLANTED
TOWARDS
BURNER
YES
CHECK
FLAME
SIGNAL
>0.6uA?
CONSULT
BOILER
MFGR.
FOR
SPECIFIC
INSTRUCTIONS.
REQUIRES
SPECIAL
TOOLS.
YES
REPLACE IBC
RESTORE
IGNITER/SENSOR
TO CORRECT
POSITION.
DO NOT RELOCATE.
OXIDE
COATING
ON
IGNITER
PREVENTING
FLAME
SIGNAL.
REPLACE
IGNITER/SENOR.