Additional Lp Connection Requirements; Lp Conversion; Gas Supply Pressure; Manifold Gas Pressure Adjustment - ICP N9MP1 Installation Instructions Manual

90+ single stage category iv furnance, fan assisted, director non-direct vent gas furnace
Hide thumbs Also See for N9MP1:
Table of Contents

Advertisement

Additional LP Connection Requirements
1.
Have a licensed
LP gas dealer
make all connections
at stor-
age tank and check
all connections
from tank to furnace.
2.
If copper
tubing
is used, it MUST complywith
limitation
set in
National
Fuel Gas Code or CGA codes.
3.
Two-stage
regulation
of LP gas is recommended.
LP Conversion
An accessory
kit shall be used to convert
to propane
gas use, see
the furnace
rating
plate for the LP conversion
accessory
kit part
number.
Do NOT allow minimum gas supply pressure to vary down-
ward. Doing so will decrease input to furnace. Refer to
Table 7, Table 8, Table 9, Table 10 and Table 11 for nor-
mal gas supply and manifold pressures.
Gas Supply Pressure
Gas supply pressure should be within minimum and maximum val-
ues listed on rating plate. Pressures are usually set by gas suppli-
ers.
Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners oper-
ating.
FIRE, EXPLOSION,
UNIT DAMAGE
HAZARD.
Failure
to follow
this warning
can
result
in
death,
property
damage
and/or
personal
injury.
An LP conversion
accessory
kit is required
when operating
the furnace
with
LP gas.
Alternate BTUH Input Ratings(USA Only)
The input rating
of these furnaces
can be changed
from the stan-
dard input rating to the alternate
input rating shown
in Table
7, by
changing
the main
burner
orifices.
Changing
of burner
orifices
MUST
be done
by a qualified
service
technician.
See section
on
changing
orifices
or following
page.
I
Alternate
Input Ratings, USA ONLY.
BTUH
Standard
Rating
50,000
75,000
100,000
125,000
BTUH
Alternate
Rating
40,000
60,000
80,000
100,000
Natural
Gas
Orifice*
#44
#44
#44
#44
LP
Gas
Orifice**
#55
#55
#55
#55
* See Table 10 for High Altitude.
** See Table 11 for High Altitude
Supply Pressure
ELECTRICAL
SHOCK HAZARD.
Failure to do so could
result in death or personal
injury.
Turn OFF power to furnace before changing
speed
taps.
1,
2.
3.
4.
Remove
the burner
compartment
door.
With gas OFF, connect
manometer
to tapped
opening
on
gas valve.
See Figure
38. Use manometer
with a 0 to 15"
water
column
range.
Turn gas ON. Operate
the furnace
by using a jumper
wire on
the R to W thermostat
connections
on the control.
Remove
manifold
pressure
adjustment
screw cover
on fur-
nace gas control
valve.
Turn adjusting
screw counterclock-
wise
to decrease
manifold
pressure
and
clockwise
to
increase
pressure.
iiiiiiiiiiiiil;;i;
¸i¸i iil ¸i !!!;;;
iiiiiiil ;;iiiiiii!i!
!! ! !!ii!iil
!;
Typical
Gas Control
Valve
Honeywell
Regulator Adjustment
Under Ca
Inlet
Pressure
Tap 1/8NPT
HONEYWELL
©o
b
Outlet
Pressure
Tap
1/8NPT
/
OUTLET
25-24-98a
FIRE HAZARD
Failure to properly set input pressure could result in
death, personal
injury and/or property
damage.
Do NOT set input rating above that shown on rating
plate.
1,
2,
A 1/8"
NPT plugged
tapping,
accessible
for a test gauge
II
connection,
must be installed
immediately
upstream
of the
I
gas supply
connection
to the furnace.
Gas input to burners
MUST
NOT exceed
the rated
input
shown
on rating
plate.
NOTE: Adjustment screw cover MUST be replaced on gas control
valve before reading manifold pressure and operating furnace.
5.
Set manifold
pressure
to value shown
in Table
8, Table
9,
Table
10 or Table
11.
6.
When the manifold
pressure
is properly
set, replace
the ad-
justment
screw
cover on the gas control
valve.
7.
Remove
jumper
wire
from thermostat
connection
on the
control
board.
Remove
manometer
connection
from man-
ifold pressure
tap, and replace
plug in gas valve.
8.
Check
for leaks
at plug.
9.
Replace
the burner
compartment
door.
[_1
44001 102102

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents