Broadband Ferro Power Supply User’s Guide 60V/87V Model Effective: June, 2003 ® Alpha Technologies...
Page 2
Power Alpha Technologies. Protecting The Power in Communications.
Page 3
Alpha Technologies or your nearest Alpha representative. NOTE Alpha denies responsibility for any damage or injury involving its enclosures, power supplies, generators, batteries, or other hardware when used for an unintended purpose, installed or operated in an unapproved manner, or improperly maintained.
WARNINGS & CAUTIONS WARNINGS A “Warning” identifies conditions and actions that pose a hazard to the user. NOTE This power supply and its associated hardware (enclosure, cabling) may contain equipment(s), or parts which have accessible hazardous voltage or currents. To avoid injury : •...
Do not install damaged equipment. Carefully inspect each package for evidence of damage during transit. If items are damaged, report any damage to the shipping company and the local Alpha sales or service office immediately. After inspection by the shipping company and a written appraisal of the damage has been received, inform Alpha Technologies that you intend to return the merchandise and request a return authorization number.
3. Installation Pole Mount Installation Procedure This section contains instructions for pole and ground mount, including electrical connections. A bucket truck or other suitable equipment such as spikes and safety harnesses, should be used during installation or service of pole-mounted cabinets. To mount the Broadband Ferro power supply to a utility pole, perform the following steps: NOTE Pole mounting the cabinet should be done in accordance with the local agreement...
3. Installation Ground Mount Installation Procedure Although ground mounting the power supply can be accomplished by several methods, the following procedure is recommended. 1. Select an appropriate site. Remove turf and level an area of approximately 24" x 24". 2. In accordance with local codes, install the disconnect box near the AC power source. NOTE The disconnect box should have a high-magnetic type circuit breaker, capable of passing short duration inrush currents, and have a 20A minimum rating (10A for...
3. Installation Electrical Connections To connect the wiring, perform the following steps: WARNING Verify the utility disconnect is off and that no conductors are energized before proceeding. 1. Open the housing cover and place a screwdriver blade in the small notch at the top of the housing to hold the cover in place.
Page 13
3. Installation Electrical Connections, continued 5. Install a weatherproof conduit fitting in the utility knockout and pull the AC primary wiring into the cabinet. 6. Connect the AC high input (black) to the copper receptacle terminal, the AC neutral input (white) to the silver receptacle, and the utility protective ground (green) to the green receptacle terminal.
4. Operation Initial Start Up 1. Turn the utility disconnect on, and power will be applied to the cable at this time. 2. If desired, use a true RMS meter to record AC output voltage at the cable output conductor (yellow wire) and the cable ground. Operation The Lectro Broadband Ferro Power Supply is designed to provide regulated 60V, or 87V output from the 120Vac power line (230Vac for 50Hz units).
5. Maintenance CAUTION Lethal voltages are present underneath the chassis when the unit is in operation. For safety, be certain to unplug the input cord and the output cable before attempting service. NOTE Part of the unit’s thermal design is heat conduction from the transformer brackets to the cabinet of the power supply.