Section 3. POWERING THE SYSTEM
Primary Power
Back-Up Power
Earth Ground
Connections
Ð 12 Ð
Power to the Control panel is supplied by model No. 1361* Plug-in Transformer
which is rated at 16.5VAC, 40VA. Caution must be taken when wiring this
transformer to the panel to guard against blowing the fuse inside the transformer
(non-replaceable).
* NOTE: Use 1361CN Transformer in Canadian installations.
In the event of an AC power loss, the Control panel is supported by a back-up,
rechargeable gel cell battery. Ademco 467 (12V, 4AH), YUASA NP4-12 (12V,
4AH) and NP7-12 (12V, 7AH) batteries are recommended. Do not use Gates
batteries.
The standby battery is automatically tested every 24 hours, beginning 24 hours
after exiting programming mode. In addition, entry into the test mode will cause a
battery test to be initiated.
Battery Standby Table
AUX. STANDBY CURRENT DRAW
AMP-HRS.
200mA 400mA 600mA 750mA
4.0
6 hrs.
4 hrs.
6.0-7.0
11 hrs. 7 hrs.
In order for the lightning transient protective devices in this product to be
effective, the designated earth ground terminal must be terminated in a good
earth ground. The following are examples of good earth grounds available at most
installations:
Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is
recommended) firmly secured to the pipe to which the ground lead is electrically
connected and secured.
AC Power Outlet Ground: Available from 3-prong, 120VAC, power outlets
only. To test the integrity of the ground terminal, use a three-wire circuit tester
with neon lamp indicators, such as the UL-Listed Ideal Model 61-035, or
equivalent, available at most electrical supply stores.
PRIMARY POWER
Supplied by 1361*
Plug-in
Connect to
12VDC, 4AH
Transformer which
or 12VDC, 7AH
is rated at
GEL CELL
16.5VAC, 40VA.
BATTERY
Caution must be
CHARGING
taken when wiring
VOLTAGE
13.7 VDC
this transformer to
the panel to guard
Replace
every
against blowing the
3 years
fuse inside the
transformer (non-
replaceable).
WHEN POWERING UP
THE PANEL, PLUG THE
TRANSFORMER IN BEFORE
CONNECTING THE BATTERY.
AC POWER AND BATTERY CONNECTIONS
3 hrs.
2.5 hrs.
5.5 hrs. 4 hrs.
BATTERY
TABS
1
2
3
Connect to
24hr. 120VAC,
60 Hz Outlet
TRANSFORMER
16.5VAC, 40VA
ADEMCO No.1361
(IN CANADA
USE No. 1361CN)
or 4300 IF
X-10 DEVICES
WILL BE USED
NOTE:
N O T E : These figures are
approximate, and may vary
depending upon the age, quality,
and capacity of the battery at
the time of the AC loss.