Summary of Contents for Generac Power Systems 04673-2
Page 1
Installation and Owner’s Manual Air-cooled Automatic Standby Generators Models: 04673-2 (6 kW NG, 7 kW LP) 04674-2 (12 kW NG, 12 kW LP) 04675-3 (13 kW NG, 15 kW LP) GENERAC POWER SYSTEMS, INC. *This manual should remain with the unit.* Not intended for use as Primary Power in place of utility or in life-support applications.
If any portion of this manual is not understood, contact • 04673-2 – 6 kW NG, 7 kW LP , single-cylinder GH- the nearest Authorized Dealer for starting, operating 410 Engine and servicing procedures.
IMPORTANT SAFETY INSTRUCTIONS Air-cooled 7 kW, 12 kW and 15 kW Generators SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment. WARNING: GENERAL HAZARDS The engine exhaust from this product...
IMPORTANT SAFETY INSTRUCTIONS Air-cooled 7 kW, 12 kW and 15 kW Generators place before operating the generator. If work must be done around an operating unit, stand on an EXPLOSION HAZARDS insulated, dry surface to reduce shock hazard. • Do not handle any kind of electrical device while •...
Section 1 — General Information Air-cooled 7 kW, 12 kW and 15 kW Generators PROTECTION SYSTEMS DANGER Unlike an automobile engine, the generator may have to run for long periods of time with no operator pres- Only qualified electricians or contractors should ent to monitor engine conditions.
Section 1 — General Information Air-cooled 7 kW, 12 kW and 15 kW Generators FUEL REQUIREMENTS 3. Remove the battery (if installed). 4. Disconnect wire #0 and wire #14 from the gas AND RECOMMENDATIONS solenoid on top of the demand regulator. With LP gas, use only the vapor withdrawal 5.
Section 1 — General Information Air-cooled 7 kW, 12 kW and 15 kW Generators 1. Turn off the gas supply. (if connected) 14. It may be necessary to make minor adjustments to the preset adjustment screw settings to achieve 2. Open the roof and remove the door. maximum power, particularly at higher altitudes.
Section 1 — General Information Air-cooled 7 kW, 12 kW and 15 kW Generators 1.10 BATTERY INSTALLATION NOTE: Fill the battery with the proper electrolyte fluid if The generator is equipped with a battery trickle necessary and have the battery fully charged before charger that is active when the unit is set up for installing it.
Section 2 — Post Installation Start-up and Adjustments Air-cooled 7 kW, 12 kW and 15 kW Generators CHECK TRANSFER SWITCH The following procedures are to be observed: • Wear full eye protection and protective clothing; OPERATION • Where electrolyte contacts the skin, wash it off Refer to Section 3.5 of the owner’s manual for manu- immediately with water;...
Section 2 — Post Installation Start-up and Adjustments Air-cooled 7 kW, 12 kW and 15 kW Generators 8. Connect an accurate AC voltmeter and a fre- 8. Turn ON electrical loads. Apply an electrical load quency meter across transfer switch terminal equal to the full rated wattage/amperage capacity lugs E1 and E2.
Section 2 — Post Installation Start-up and Adjustments Air-cooled 7 kW, 12 kW and 15 kW Generators ADJUSTING THE REGULATOR 6. When the highest frequency is reached maximum power has been set. Then turn both adjustment (NATURAL GAS ONLY) screws 1/4 turn counterclockwise. Regulator is now set.
Section 2 — Post Installation Start-up and Adjustments Air-cooled 7 kW, 12 kW and 15 kW Generators 6. When frequency is correct at no load, check the 7. Restart the unit. AC voltage reading. If voltage is incorrect, the volt- 8.
Section 3 — Operation Air-cooled 7 kW, 12 kW and 15 kW Generators NOTE: Figure 3.1 – Generator Control Panel The voltage regulator is housed above the generator's control panel. The regulator maintains a voltage in FUSE L o c a t e y o u r n e a r e s t d e a le r a t : direct proportion to frequency.
Section 3 — Operation Air-cooled 7 kW, 12 kW and 15 kW Generators Upon restoration of utility source voltage above a DANGER preset level, generator circuit board action signals the transfer switch to transfer loads back to that power Do not attempt to activate the transfer switch supply.
Section 3 — Operation Air-cooled 7 kW, 12 kW and 15 kW Generators PROTECTION SYSTEMS DANGER 3.7.1 LOW OIL PRESSURE SWITCH Do not attempt to activate the transfer switch This switch (Figure 3.3) has normally closed con- manually until all power voltage supplies tacts that are held open by engine oil pressure during to the switch have been positively turned off.
Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators 3.7.3.1 Approximate Crank Cycle Times 2. Remove the dipstick and wipe it dry with a clean cloth. • 15 seconds ON 3. Install the dipstick; then, remove it again. The oil •...
Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators CHANGING THE ENGINE OIL CHANGING THE OIL FILTER Change the engine oil filter as follows: 4.3.1 ENGINE OIL RECOMMENDATIONS 1. With the oil drained, remove the old oil filter by Use oil of American Petroleum Institute (API) Service turning it counterclockwise.
Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators BATTERY MAINTENANCE Figure 4.7 — 12 kW and 15 kW Engine Air Cleaner The battery should be inspected per the “Service Schedule,” Section 4.13. The following procedure Screw should be followed for inspection: 1.
Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators following procedures are to be followed: Figure 4.10 - Valve Clearance Adjustment • DO NOT SMOKE when near the battery; Rocker • DO NOT cause flame or spark in battery area; and Pivot Ball •...
Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators 4.12.2 RETURN TO SERVICE To return the unit to service after storage, proceed as The exhaust from this product gets extremely follows: hot and remains hot after shutdown. High grass, 1.
Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators 4.13 SERVICE SCHEDULE ATTENTION: It is recommended that all service work be performed by the nearest Authorized Dealer. SYSTEM/COMPONENT PROCEDURE FREQUENCY X = Action Inspect Change Clean W = Weekly R = Replace as Necessary M = Monthly...
Section 5 — Troubleshooting Air-cooled 7 kW, 12 kW and 15 kW Generators TROUBLESHOOTING GUIDE PROBLEM CAUSE CORRECTION The engine will not crank. 1. Fuse blown 1. Replace 15A fuse on generator control panel. 2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary.
Section 8 — Mounting Dimensions Air-cooled 7 kW, 12 kW and 15 kW Generators Drawing No. 0D3739-C CBHOM-F CBHOM-F CBHOM-F CBHOM-F CBHOM-F CBHOM-F TYPE HOM 120/240v TYPE HOM 120/240v TYPE HOM 120/240v TYPE HOM 120/240v TYPE HOM 120/240v TYPE HOM 120/240v...
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period.
Page 55
Section 10 – Warranty Air-cooled 7 kW, 12 kW and 15 kW Generators EMISSION CONTROL SYSTEM WARRANTY Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
Page 56
FOR GENERAC RESIDENTIAL AND LIGHT COMMERCIAL UNITS For a period of two (2) years or two thousand (2,000) hours of operation from the date of sale, which ever occurs first, Generac Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below.
ERRATA SHEET ALL 8.5 kW THROUGH 15 kW HOME STAND-BY GENERATORS WITH GT-990/760 ENGINES 2/24/06 ! IMPORTANT INFORMATION ! THE SPARK PLUG GAP FOR ALL 8.5 kW THROUGH THE 15 kW HOME STAND-BY GENERATORS WITH THE GT-990/760 ENGINES SHOULD BE SET AT 1.02 mm (0.040 inch).
Need help?
Do you have a question about the 04673-2 and is the answer not in the manual?
Questions and answers