Specifications; Ratings - Omron E5AN User Manual

Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

SPECIFICATIONS

JRatings
Supply voltage
Operating voltage range
Power
consumption
Sensor input
Control
Relay output
output
Voltage output
(PNP)
Current output DC 4-20 mA load 600
Alarm output
Control method
Setting method
Indication method
Other functions
Ambient temperature
Ambient humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
F HBA
Max. heater current
Input current readout accuracy
Heater burnout alarm setting range
Min. detection ON time
A–2
100 to 240 VAC, 50/60 Hz
85 to 110% of rated supply voltage
9 VA
Thermocouple
Platinum resistance thermometer : Pt100, JPt100
Non-contact temperature sensor : K10 to 70_C, K60 to 120_C, K115 to 165_C,
Voltage input: 0 to 50 mV
SPST-NO, 250 VAC 5 A (resistive load), electrical life : 100,000 operations
Min. applicable load 5V 10 m
"15%FS, max. load current 21 mA
DC 12V
+15
DC 12V
%FS, max. load current 40 mA
–20
With short circuit protection circuit.
max. resolution approx.2,600
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations
Min. applicable load 1V 1 mA
2-PID or ON/OFF control
Digital setting using front panel keys
7-segment digital display and single-lighting indicator
According to controller model
-10 to 55_C (with no condensation or icing)
Relative humidity 25 to 85%
-25 to 65_C (with no condensation or icing)
2,000 m or less
T2A, 250 VAC, time lag, low shut–off capacity
Installation Category II, Pollution Class 2 (IEC 61010–1 compliant)
Single-phase AC 50 A
5%FS 1 digit max.
0.1 to 49.9 A (0.1 A units)
0.0 A
: Heater burnout alarm output turns OFF.
50.0 A
: Heater burnout alarm output turns ON.
190 ms
24 VAC, 50/60 Hz/24 VDC
5 VA/4 W
: K, J, T, E, L, U, N, R, S, B
K160 to 260_C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents